5
Fig. 5 — Dimensions, 09DK044
COIL CONNECTION DIMENSIONS — MM [IN.]
NOTES:
1. There must be 1220 mm [4-0] for service and for unrestricted airflow on
all sides of unit.
2. There must be minimum 2440 mm [8-0] clear air space above unit.
3. The approximate operating weight of the unit follows:
4. Dimensions are in mm. Dimensions in [ ] are in feet-inches.
5. Dimension “E” for 34.9 mm I.D. is 118 mm [4
5
/
8
].
Dimension “E” for 28.5 mm I.D. is 112 mm [4
7
/
16
].
UNIT
09DK
ABCD E
044
34.9 I.D.
[1
3
/
8
]
28.5 I.D.
[1
1
/
8
]
22.2 I.D.
[
7
/
8
]
15.9 I.D.
[
5
/
8
]
SEE
NOTE #5
UNIT 09DK
TOTAL
WEIGHT
OPERATING WT. AT SUPPORT
POINTS
Lb Kg Lb Kg Lb Kg
044 1676 760.2 391 177.4 447 202.8
044C 1984 900.0 462 209.6 529 240.0
C—Units with optional copper-fin coils
1&2
3&4

Related product manuals