Table 2 — LID Display Data (cont)
EXAMPLE2—STATUS02 DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
.
2. Press STATUS
.
3. Scroll down to highlight STATUS02.
4. Press SELECT
.
DESCRIPTION
POINT TYPE
UNITS
REFERENCE POINT NAME
(ALARM HISTORY)
INPUT OUTPUT
Hot Gas Bypass Relay X OFF/ON HGBR
*Chilled Water Pump X OFF/ON CHWP
Chilled Water Flow X NO/YES EVFL
*Condenser Water Pump X OFF/ON CDP
Condenser Water Flow X NO/YES CDFL
Compressor Start Relay X OFF/ON CMPR
Compressor Start Contact X OPEN/CLOSED 1CR AUX
Compressor Run Contact X OPEN/CLOSED RUN AUX
Starter Fault Contact X OPEN/CLOSED STR FLT
Pressure Trip Contact X OPEN/CLOSED PRS TRIP
Single Cycle Dropout X NORMAL/ALARM V1 CYCLE
Oil Pump Relay X OFF/ON OILR
Oil Heater Relay X OFF/ON OILH
Motor Cooling Relay† X OFF/ON MTRC
Auxiliary Oil Pump Relay X OFF/ON AUXOILR
*Tower Fan Relay X OFF/ON TFR
Compr. Shunt Trip Relay X OFF/ON TRIPR
Alarm Relay X NORMAL/ALARM ALM
Spare Prot Limit Input X ALARM/NORMAL SPR PL
†Information is applicable to hermetic machines only.
NOTE: values preceded by an asterisk (*) can be forced (changed by an operator) from the LID screen
or from another control device (such as a Carrier Comfort Network [CCN] terminal).
EXAMPLE3—STATUS03 DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
.
2. Press STATUS
.
3. Scroll down to highlight STATUS03.
4. Press SELECT
.
DESCRIPTION RANGE UNITS
REFERENCE POINT NAME
(ALARM HISTORY)
OPTIONS BOARD 1
*Demand Limit 4-20 mA 4-20 mA DEM OPT
*Temp Reset 4-20 mA 4-20 mA RES OPT
*Common CHWS Sensor –40-245 (–40-118) DEG F (DEG C) CHWS
*Common CHWR Sensor –40-245 (–40-118) DEG F (DEG C) CHWR
*Remote Reset Sensor –40-245 (–40-118) DEG F (DEG C) R RESET
*Temp Sensor — Spare 1 –40-245 (–40-118) DEG F (DEG C) SPARE1
*Temp Sensor — Spare 2 –40-245 (–40-118) DEG F (DEG C) SPARE2
*Temp Sensor — Spare 3 –40-245 (–40-118) DEG F (DEG C) SPARE3
OPTIONS BOARD 2
*4-20 mA — Spare 1 4-20 mA SPARE1 M
*4-20 mA — Spare 2 4-20 mA SPARE2 M
*Temp Sensor — Spare 4 –40-245 (–40-118) DEG F (DEG C) SPARE4
*Temp Sensor — Spare 5 –40-245 (–40-118) DEG F (DEG C) SPARE5
*Temp Sensor — Spare 6 –40-245 (–40-118) DEG F (DEG C) SPARE6
*Temp Sensor — Spare 7 –40-245 (–40-118) DEG F (DEG C) SPARE7
*Temp Sensor — Spare 8 –40-245 (–40-118) DEG F (DEG C) SPARE8
*Temp Sensor — Spare 9 –40-245 (–40-118) DEG F (DEG C) SPARE9
NOTE: values preceded by an asterisk (*) can be forced (changed by an operator) from the LID screen
or from another control device (such as a Carrier Comfort Network [CCN] terminal).