Table 12 LID Primary and Secondary Messages and Custom Alarm/Alert Messages
with Troubleshooting Guides (cont)
I. NORMAL RUN WITH RESET, TEMPERATURE, OR DEMAND
PRIMARY MESSAGE SECONDARY MESSAGE PROBABLE CAUSE/REMEDY
RUNNING RESET ACTIVE 4-20MA SIGNAL
Reset program active based on CONFIG screen setup.RUNNING RESET ACTIVE REMOTE SENSOR CONTROL
RUNNING RESET ACTIVE CHW TEMP DIFFERENCE
RUNNING TEMP CONTROL LEAVING CHILLED WATER Default method of temperature control.
RUNNING TEMP CONTROL ENTERING CHILLED WATER ECW control activated on CONFIG screen.
RUNNING TEMP CONTROL TEMPERATURE RAMP LOADING Ramp loading in effect. Use SERVICE1 screen to modify.
RUNNING DEMAND LIMITED BY DEMAND RAMP LOADING Ramp loading in effect. Use SERVICE1 screen to modify.
RUNNING DEMAND LIMITED BY LOCAL DEMAND SETPOINT Demand limit set point is , actual demand.
RUNNING DEMAND LIMITED BY 4-20MA SIGNAL
Demand limit is active based on CONFIG screen setup.RUNNING DEMAND LIMITED BY CCN SIGNAL
RUNNING DEMAND LIMITED BY LOADSHED/REDLINE
RUNNING TEMP CONTROL HOT GAS BYPASS
Hot gas bypass option is energized. See surge prevention in the
control section.
RUNNING DEMAND LIMITED BY LOCAL SIGNAL Active demand limit manually overridden on STATUS01 table.
RUNNING TEMP CONTROL ICE BUILD MODE Chiller is running under Ice Build temperature control.
J. NORMAL RUN OVERRIDES ACTIVE (ALERTS)
PRIMARY MESSAGE SECONDARY MESSAGE ALARM MESSAGE/PRIMARY CAUSE ADDITIONAL CAUSE/REMEDY
RUN CAPACITY LIMITED HIGH CONDENSER PRESSURE CRP [VALUE] exceeded limit of [LIMIT]*.
Condenser pressure override.
See Capacity Overrides, Table 4.
Correct operating condition, modify set-
point, or release override.
RUN CAPACITY LIMITED HIGH MOTOR TEMPERATURE MTRW [VALUE] exceeded limit of [LIMIT]*.
Motor temperature override.
RUN CAPACITY LIMITED LOW EVAP REFRIG TEMP ERT [VALUE] exceeded limit of [LIMIT]*. Check
refrigerant charge level.
RUN CAPACITY LIMITED HIGH COMPRESSOR LIFT Surge Prevention Override; lift too high for
compressor.
RUN CAPACITY LIMITED MANUAL GUIDE VANE TARGET GV TRG Run Capacity Limited: Manual guide
vane target.
*[LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or alarm condition. [VALUE]
is the actual temperature, pressure, voltage, etc., at which the control tripped.
K. OUT-OF-RANGE SENSOR FAILURES
PRIMARY MESSAGE SECONDARY MESSAGE ALARM MESSAGE/PRIMARY CAUSE ADDITIONAL CAUSE/REMEDY
SENSOR FAULT LEAVING CHW TEMPERATURE Sensor Fault: Check leaving CHW
sensor.
See sensor test procedure and check
sensors for proper operation and
wiring.
SENSOR FAULT ENTERING CHW TEMPERATURE Sensor Fault: Check entering CHW
sensor.
SENSOR FAULT CONDENSER PRESSURE Sensor Fault: Check condenser pressure
transducer.
SENSOR FAULT EVAPORATOR PRESSURE Sensor Fault: Check evaporator pressure
transducer.
SENSOR FAULT BEARING TEMPERATURE Sensor Fault: Check bearing temperature
sensor.
SENSOR FAULT MOTOR WINDING TEMP Sensor Fault: Check motor temperature
sensor.
SENSOR FAULT DISCHARGE TEMPERATURE Sensor Fault: Check discharge temperature
sensor.
SENSOR FAULT OIL SUMP TEMPERATURE Sensor Fault: Check oil sump temperature
sensor.
SENSOR FAULT OIL PRESSURE TRANSDUCER Sensor Fault: Check oil pressure
transducer.
89