33
CONDENSER ONLY RATINGS*
SST
°F(°C)
CONDENSER ENTERING AIR TEMPERATURES ° F (° C)
55 (12.78) 65 (18.33) 75 (23.89) 85 (29.44) 95 (35.0) 105 (40.56) 115 (46.11) 125 (51.67)
24APA724 HI
30
(---1.11)
TCG 22.50 21.30 20.20 18.90 17.60 16.30 14.90 13.40
SDT 67.50 77.40 87.20 97.00 106.80 116.70 126.60 136.70
KW 1.00 1.16 1.33 1.50 1.69 1.91 2.15 2.44
35
(1.67)
TCG 24.90 23.60 22.30 20.90 19.50 18.10 16.50 15.00
SDT 68.70 78.50 88.20 98.00 107.80 117.60 127.50 137.60
KW 1.02 1.18 1.35 1.52 1.72 1.93 2.18 2.47
40
(4.44)
TCG 27.40 26.00 24.60 23.10 21.50 20.00 18.30 16.60
SDT 70.00 79.70 89.40 99.10 108.80 118.50 128.40 138.50
KW 1.05 1.20 1.37 1.55 1.74 1.96 2.21 2.50
45
(7.22)
TCG 30.10 28.60 27.00 25.40 23.70 22.00 20.30 18.50
SDT 71.30 80.90 90.50 100.20 109.80 119.60 129.40 139.40
KW 1.07 1.23 1.39 1.57 1.76 1.99 2.24 2.53
50
(10.0)
TCG 33.10 31.40 29.70 27.90 26.10 24.20 22.40 20.40
SDT 72.60 82.10 91.70 101.30 111.00 120.60 130.40 140.40
KW 1.09 1.25 1.41 1.59 1.79 2.01 2.27 2.57
55
(12.78)
TCG 36.20 34.40 32.50 30.60 28.60 26.60 24.60 22.50
SDT 74.00 83.50 93.00 102.50 112.10 121.80 131.50 141.40
KW 1.12 1.28 1.44 1.62 1.82 2.04 2.30 2.61
60
(15.56)
TCG 39.60 37.60 35.50 33.50 31.30 29.20 27.00 24.70
SDT 75.50 84.90 94.30 103.80 113.40 122.90 132.60 142.40
KW 1.15 1.31 1.47 1.65 1.85 2.08 2.34 2.64
24APA724 LO
30
(---1.11)
TCG 14.10 13.30 12.50 11.6 10.70 9.80 8.80 7.70
SDT 61.60 71.30 81.00 90.8 100.50 110.20 119.90 129.50
KW 0.64 0.78 0.93 1.10 1.26 1.47 1.71 1.99
35
(1.67)
TCG 16.00 15.10 14.20 13.20 12.20 11.20 10.10 9.00
SDT 62.40 72.10 81.80 91.50 101.20 110.80 120.50 130.10
KW 0.65 0.79 0.94 1.10 1.27 1.48 1.72 2.01
40
(4.44)
TCG 17.90 17.00 16.00 14.90 13.80 12.70 11.50 10.30
SDT 63.30 72.90 82.60 92.20 101.90 111.50 121.10 130.70
KW 0.67 0.81 0.95 1.11 1.29 1.49 1.73 2.02
45
(7.22)
TCG 20.10 19.00 17.90 16.80 15.60 14.40 13.10 11.70
SDT 64.20 73.80 83.50 93.10 102.60 112.20 121.80 131.40
KW 0.68 0.82 0.96 1.12 1.30 1.50 1.75 2.03
50
(10.0)
TCG 22.40 21.30 20.10 18.80 17.50 16.20 14.70 13.30
SDT 65.30 74.80 84.40 93.90 103.50 113.00 122.50 132.00
KW 0.70 0.84 0.98 1.13 1.31 1.51 1.76 2.04
55
(12.78)
TCG 24.90 23.70 22.40 21.00 19.60 18.10 16.60 15.00
SDT 66.40 75.90 85.30 94.90 104.30 113.70 123.20 132.70
KW 0.73 0.86 1.00 1.15 1.32 1.53 1.77 2.05
60
(15.56)
TCG 27.70 26.30 24.80 23.30 21.80 20.20 18.50 16.80
SDT 67.60 77.00 86.40 95.80 105.20 114.60 124.00 133.40
KW 0.75 0.88 1.01 1.16 1.34 1.54 1.78 2.06
24APA736 HI
30
(---1.11)
TCG 32.00 30.20 28.40 26.50 24.50 22.50 20.50 18.40
SDT 71.10 80.40 89.80 99.20 108.60 118.00 127.40 137.00
KW 1.51 1.72 1.95 2.18 2.44 2.73 3.06 3.43
35
(1.67)
TCG 35.60 33.60 31.60 29.50 27.40 25.20 23.00 20.80
SDT 72.60 81.80 91.20 100.50 109.80 119.20 128.60 138.10
KW 1.55 1.76 1.98 2.22 2.48 2.77 3.11 3.49
40
(4.44)
TCG 39.40 37.30 35.10 32.80 30.50 28.20 25.80 23.40
SDT 74.20 83.40 92.60 101.90 111.20 120.50 129.80 139.30
KW 1.59 1.80 2.02 2.26 2.52 2.82 3.16 3.54
45
(7.22)
TCG 43.60 41.20 38.80 36.40 33.90 31.40 28.80 26.30
SDT 76.00 85.10 94.20 103.40 112.60 121.90 131.10 140.50
KW 1.63 1.84 2.06 2.30 2.57 2.87 3.21 3.60
50
(10.0)
TCG 48.00 45.40 42.80 40.20 37.50 34.80 32.10 29.30
SDT 77.80 86.80 95.90 105.00 114.10 123.30 132.50 141.70
KW 1.68 1.89 2.11 2.35 2.62 2.93 3.27 3.66
55
(12.78)
TCG 52.70 49.90 47.10 44.30 41.40 38.50 35.60 32.60
SDT 79.80 88.70 97.70 106.70 115.70 124.80 133.80 143.00
KW 1.73 1.94 2.16 2.40 2.68 2.98 3.33 3.72
60
(15.56)
TCG 57.80 54.70 51.70 48.70 45.60 42.50 39.30 36.10
SDT 81.90 90.70 99.50 108.40 117.30 126.30 135.20 144.20
KW 1.79 1.99 2.21 2.46 2.73 3.04 3.39 3.79
See notes on page 31