EasyManuals Logo

Carrier 24APA7 Performance User Manual

Carrier 24APA7 Performance
38 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #5 background imageLoading...
Page #5 background image
5
ELECTRICAL DATA
U n i t S i z e ---
Voltage,
Series
V/PH
OPER VOLTS* COMPR FAN
MCA
MIN
WIRE
SIZE{
MIN
WIRE
SIZE{
MAX
LENGTH
ft. (m)}
MAX
LENGTH
ft. (m)}
MAX
FUSE** or
CKT BRK
AMPS
MIN MAX RLA LRA FLA 60° C 75° C 60° C 75° C
24--- 30 208/230
187 253
10.30 52.0 0.7 13.58 14.00 14.00 60 (18.3) 57 (17.4) 20
36--- 30 208/230 16.70 82.0 1.2 22.08 12.00 12.00 57 (17.4) 54 (16.5) 35
48--- 31 208/230 21.20 96.0 1.3 27.80 10.00 10.00 72 (21.9) 68 (20.7) 40
60--- 31 208/230 23.00 118.0 1.3 30.06 8.00 10.00 93 (28.3) 57 (17.4) 50
* Permissible limits of the voltage range at which the unit will operate satisfactorily
{ If wire is applied at ambient greater than 30_C, consult table 310 ---16 of the NEC (NFPA 70). The ampacity of non---metallic---sheathed cable (NM), trade
name ROMEX, shall be that of 60_C conditions, per the NEC (NFPA 70) Article 336---26. If other than uncoated (no---plated), 60 or 75_C insulation, copper
wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (NFPA 70).
} Length shown is as measured one way along wire path between unit and service panel for voltage drop not to exceed 2%.
* * T i m e --- D e l a y f u s e .
FLA --- Fu l l L o a d A m p s
LRA --- L o c k e d R o t o r A m p s
MCA --- Minimum Circuit Amps
RLA ---RatedLoadAmps
NOTE: Control circuit is 24---V on all units and requires external power source. Copper wire must be used from service disconnect to unit.
All motors/compressors contain internal overload protection.
Complies with 2007 requirements of ASHRAE Standards 90.1
A--WEIGHTED SOUND POWER (dBA)
U n i t S i z e ---
Voltage, Series
Standard Rating
(dBA)
TYPICAL OCTAVE BAND SPECTRUM (dBA, without tone adjustment)
125 250 500 1000 4000 8000
24 --- 30
7 1 --- l o w st a g e 49.4 61.4 60.8 61.5 55.5 46.9
7 2 --- h i g h s t a g e 49.9 58.4 61.8 60.0 56.0 50.4
36 --- 30
7 2 --- l o w st a g e 48.9 57.9 64.3 62.0 55.5 50.9
7 4 --- h i g h s t a g e 49.4 59.4 62.3 64.0 56.5 52.4
48 --- 31
7 4 --- l o w st a g e 53.9 63.9 61.8 64.0 56.0 47.9
7 4 --- h i g h s t a g e 52.9 60.9 61.8 64.0 60.0 48.9
60 --- 31
7 3 --- l o w st a g e 51.9 58.9 65.3 61.5 55.0 48.4
7 3 --- h i g h s t a g e 52.4 61.4 62.3 64.0 56.0 49.9
NOTE: Tested in accordance with AHRI Standard 270---08. (Not listed with AHRI).
CHARGING SUBCOOLING (TXV--TYPE EXPANSION DEVICE)
UNIT SIZE--- VOLTAGE, SERIES REQUIRED SUBCOOLING _F(_C)
24--- 30 10 (5.6)
36--- 30 10 (5.6)
48--- 31 10 (5.6)
60--- 31 10 (5.6)
CONTROLS / THERMOSTATS
Infinity Controls DESCRIPTION
SYSTXCCUIZ01 ---B Infinity System Zone Control User Interface
SYSTXCCUID01 ---B Infinity System Non---Zone Control User Interface
THERMOSTAT / SU BBASE
PKG.
DESCRIPTION
T P --- P R H 0 1 --- A Programmable Thermidistat
T P --- N R H 0 1 --- A Non--- programmable Thermidistat
T P --- P H P 0 1 * Performance Series Programmable HP Stat
T P --- N H P 0 1 * Performance Series Non--- programmable HP Stat
T C --- P H P 0 1 * Comfort Series Programmable HP Stat
T C --- N H P 0 1 * Comfort Series Non --- programmable HP Stat
*Serial numbers beginning with 2909 and thereafter.
24APA7

Other manuals for Carrier 24APA7 Performance

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier 24APA7 Performance and is the answer not in the manual?

Carrier 24APA7 Performance Specifications

General IconGeneral
BrandCarrier
Model24APA7 Performance
CategoryAir Conditioner
LanguageEnglish

Related product manuals