3
PHYSICAL DATA
UNIT SIZE SERIES 18---30 24---30 30---30, 50 36---30, 50,
60
42---30, 50,
60
48---30, 50,
60
60---30,
50, 60
Operating Weight (lb) 159 160 208 211 233 269 295
Shipping W eight (lb) 184 185 240 242 262 300 327
Compressor Type Scroll
REFRIGERANT Freon® ( R --- 2 2 )
Control T X V ( R --- 2 2 H a r d S h u t o f f )
Charge (lb) 5.5 6 7.5 8 10 14 15.5
COND FAN Propeller Type, Direct Drive
Air Discharge Vertical
Air Qty (CFM) 2233 2614 2614 3334 3334 4046 4046
Motor HP 1/12 1/10 1/10 1/8 1/8 1/5 1/5
Motor RPM 800 1100 1100 800 800 800 800
COND COIL
Face Area (Sq ft) 15.09 15.09 25.87 22.63 17.6 22.63 25.15
Fins per In. 20 20 20 20 20 20 20
Rows 1 1 1 1 2 2 2
Circuits 5 6 6 6 7 8 9
VALVECONNECT.(In.ID)
Vapor 5/8” 5/8” 3/4” 3/4” 7/8” 7/8” 7/8”
Liquid 3/8”
REFRIGERANT TUBES* (In. OD)
Vapor (0---80 Ft Tube Length) 5/8” 5/8” 3/4” 3/4” 7/8” 7/8” 1--- 1/8”
Liquid (0--- 80 Ft Tube Length) 3/8”
* For tubing sets between 80 and 200 ft. horizontal or 20 ft. vertical differential, consult the Longline Guideline.
Note: See unit Installation Instruction for proper installation.
VAPOR LINE SIZING AND COOLING CAPACITY LOSS
1--STAGE HEAT PUMP APPLICATIONS
LONG LINE APPLICATION: An application is considered
”Long line” when the total equivalent tubing length exceeds 80 ft
or when there is more than 20 Ft vertical separation between
indoor and outdoor units. These applications require additional
accessories and system modifications for reliable system
operation. The maximum allowable total equivalent length is
250Ft. The maximum vertical separation is 200 Ft when outdoor
unit is above indoor unit, and 60 Ft when the outdoor unit is
below the indoor unit. Refer to Accessory Usage Guideline below
for required accessories. See Long--Line Application Guideline
for required piping and system modifications. Also, refer to the
table below for the acceptable vapor tube diameters based on the
total length to minimize the cooling capacity loss.
Unit Nominal Size (Btuh)
Acceptable
Liquid Line
Diameter
OD (in.)
Acceptable
Vapor Line
Diameter
OD (in.)
Cooling Capacity Loss (%)
Total Equivalent Line Length (ft)
Standard Application
Long Line Application
Requires Accessories
25 50 80 80+ 100 125 150 175 200 225 250
18000
R --- 2 2 H P
3/8
5/8 0 1 1 1 2 3 3 4 5 5 6
3/4 0 0 0 0 0 1 1 1 1 2 2
24000
R --- 2 2 H P
3/8
5/8 0 1 3 3 3 5 6 7 8 9 10
3/4 0 0 0 0 1 1 1 2 2 3 3
30000
R --- 2 2 H P
3/8
3/4 0 1 1 1 2 3 3 4 5 5 6
7/8 0 0 0 0 1 1 1 2 2 2 3
36000
R --- 2 2 H P
3/8
3/4 0 1 2 2 3 4 5 6 7 8 9
7/8 0 0 1 1 1 2 2 3 3 4 4
42000
R --- 2 2 H P
3/8 7/8 0 1 1 1 2 2 3 4 4 5 5
48000
R --- 2 2 H P
3/8 7/8 0 1 2 2 2 3 4 5 5 6 7
60000
R --- 2 2 H P
3/8
7/8 1 2 3 3 4 5 7 8 9 10 11
11/8 0 0 1 1 1 1 2 2 2 3 3
Standard Length = 80 Ft or less total equivalvent length
Applications in this area are long line. Accessories are required as shown recommended on Long Line Application Guidelines
Applications in this area may have height restrictions that limit allowable total equivalent length, when outdoor unit is below indoor unit See
Long Line Application Guidelines