PURONR (R410A) QUICK REFERENCE GUIDE
S Puron refrigerant operates at 5070 percent higher pressures than R22. Be sure that servicing equipment and replacement
components are designed to operate with Puron
S Puron refrigerant cylinders are rose colored.
S Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400.
S Puron systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose when
charging into suction line with compressor operating
S Manifold sets should be 700 psig high side and 180 psig low side with 550 psig lowside retard.
S Use hoses with 700 psig service pressure rating.
S Leak detectors should be designed to detect HFC refrigerant.
S Puron, as with other HFCs, is only compatible with POE oils.
S Vacuum pumps will not remove moisture from oil.
S Do not use liquidline filter driers with rated working pressures less than 600 psig.
S Do not leave Puron suction line filter driers in line longer than 72 hours.
S Do not install a suctionline filter drier in liquid line.
S POE oils absorb moisture rapidly. Do not expose oil to atmosphere.
S POE oils may cause damage to certain plastics and roofing materials.
S Wrap all filter driers and service valves with wet cloth when brazing.
S A factory approved liquidline filter drier is required on every unit.
S Do NOT use an R22 TXV.
S If indoor unit is equipped with an R22 TXV or piston metering device, it must be changed to a hard shutoff Puron TXV.
S Never open system to atmosphere while it is under a vacuum.
S When system must be opened for service, recover refrigerant, evacuate then break vacuum with dry nitrogen and replace filter
driers. Evacuate to 500 microns prior to recharging.
S Do not vent Puron into the atmosphere.
S Do not use capillary tube coils.
S Observe all warnings, cautions, and bold text.
S All indoor coils must be installed with a hard shutoff Puron TXV metering device.
Copyright 2015 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231 Edition Date: 03/15
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Catalog No: 25HCB6-5SI
Replaces: 25HCB6-4SI
25HCB6

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier 25HCB6 Performance Series and is the answer not in the manual?

Carrier 25HCB6 Performance Series Specifications

General IconGeneral
BrandCarrier
Model25HCB6 Performance Series
CategoryHeat Pump
LanguageEnglish

Related product manuals