7
Configure Control (All Sizes)
1. The control must be configured to recognize the
Energy Management Module. Using the display, press
until the screen is blank. Use the arrow keys to
select the Configuration mode LED. Follow the steps
outlined in Table 1 using the keys on the display.
2. To change the value of EMM, press until the
Marquee display screen is blank. Use the arrow keys to
light up the Configuration mode LED. Press .
Press the down arrow key until OPT1 is displayed.
Press . Press the up arrow key to select
EMM. Press to stop display at its current
value, NO. Press again and PASS WORD
will be displayed. Press to bring up the
default password of 1111. Press four times to
confirm the password. Use the arrow keys as needed if
the password is other than 1111. The NO value will
now be flashing. Press the up arrow key to change
the value to YES and to accept the change.
Table 1 — Configuration Mode Menu
ESCAPE
ESCAPE
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
MODE
(RED LED)
KEYPAD
ENTRY
SUBMODE
KEYPAD
ENTRY
ITEM DISPLAY ITEM EXPANSION COMMENTS
CONFIGURATION
DISP
UNIT
OPT1 FLUD X COOLER FLUID
HGB.S YES/NO
HOT GAS BYPASS
SELECT
HPCM X
HEAD PRESS.
CONT. METHOD
HPCT X
HEAD PRESS.
CONTROL TYPE
PRTS YES/NO
PRESSURE
TRANSDUCERS
PMP.1 ON/OFF
COOLER PUMP
INTERLOCK
CPC ON/OFF
COOLER PUMP
CONTROL
CA.UN X
NO. CIRCUIT A
UNLOADERS
CB.UN X
NO. CIRCUIT B
UNLOADERS
EMM YES/NO
EMM MODULE
INSTALLED
Default: No
Change to Yes
ENTER
ENTER