EasyManua.ls Logo

Carrier 30GTN - Page 32

Carrier 30GTN
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 8 Service Test Mode and Sub-Mode Directory
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY ITEM EXPANSION COMMENT
TEST
ENTER
ON/OFF SERVICE TEST MODE Use to Enable/Disable Manual Mode
OUTS
ENTER
FR.A1 ON/OFF FAN A1 RELAY Fan 3 (040-050)
Fans 3,4 (060-110, 230B-315B)
Fans 1,2 (130 [60 Hz])
Fan 1 (130 [50 Hz], 150, 170, 230A- 270A,
330A/B, 360B [50 Hz])
Fans 1,11 (190-210, 290A, 315A,
360A, 360B [60 Hz], 390A/B-420A/B)
FR.A2 ON/OFF FAN A2 RELAY Fans 3,9 (130 [50 Hz], 150-210,
230A-315A, 330A/B-420A/B)
EXV.A 0-100% EXV % OPEN
FR.B1 ON/OFF FAN B1 RELAY Fan 4 (040-050)
Fans 5,6 (060-090, 230B-245B)
Fans 5,6,7,8 (100,110, 255B-315B)
Fans 3,4,9,10 (130 [60 Hz])
Fan 2 (130 [50 Hz], 150, 170, 230A- 270A,
330A/B, 360B [50 Hz])
Fans 2,12 (190-210,290A,315A,
360A, 360B [60 Hz] ,390A/B-420A/B)
FR.B2 ON/OFF FAN B2 RELAY Fans 4,10 (130 [50 Hz], 150-210, 230A-315A,
330A/B-420A/B)
EXV.B 0-100% EXV % OPEN
CLR.P ON/OFF COOLER PUMP RELAY
RMT.A ON/OFF REMOTE ALARM RELAY
COMP
ENTER
CC.A1 ON/OFF COMPRESSOR A1 RELAY
CC.A2 ON/OFF COMPRESSOR A2 RELAY
CC.A3 ON/OFF COMPRESSOR A3 RELAY
CC.A4 ON/OFF COMPRESSOR A4 RELAY
UL.A1 ON/OFF UNLOADER A1 RELAY
UL.A2 ON/OFF UNLOADER A2 RELAY
HGBP ON/OFF HOT GAS BYPASS RELAY
CC.B1 ON/OFF COMPRESSOR B1 RELAY
CC.B2 ON/OFF COMPRESSOR B2 RELAY
CC.B3 ON/OFF COMPRESSOR B3 RELAY
CC.B4 ON/OFF COMPRESSOR B4 RELAY
UL.B1 ON/OFF UNLOADER B1 RELAY
UL.B2 ON/OFF UNLOADER B2 RELAY
LEGEND
EXV Electronic Expansion Valve
32

Table of Contents

Other manuals for Carrier 30GTN