Table 8 — Service Test Mode and Sub-Mode Directory
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY ITEM EXPANSION COMMENT
TEST
ENTER
ON/OFF SERVICE TEST MODE Use to Enable/Disable Manual Mode
OUTS
ENTER
FR.A1 ON/OFF FAN A1 RELAY Fan 3 (040-050)
Fans 3,4 (060-110, 230B-315B)
Fans 1,2 (130 [60 Hz])
Fan 1 (130 [50 Hz], 150, 170, 230A- 270A,
330A/B, 360B [50 Hz])
Fans 1,11 (190-210, 290A, 315A,
360A, 360B [60 Hz], 390A/B-420A/B)
FR.A2 ON/OFF FAN A2 RELAY Fans 3,9 (130 [50 Hz], 150-210,
230A-315A, 330A/B-420A/B)
EXV.A 0-100% EXV % OPEN
FR.B1 ON/OFF FAN B1 RELAY Fan 4 (040-050)
Fans 5,6 (060-090, 230B-245B)
Fans 5,6,7,8 (100,110, 255B-315B)
Fans 3,4,9,10 (130 [60 Hz])
Fan 2 (130 [50 Hz], 150, 170, 230A- 270A,
330A/B, 360B [50 Hz])
Fans 2,12 (190-210,290A,315A,
360A, 360B [60 Hz] ,390A/B-420A/B)
FR.B2 ON/OFF FAN B2 RELAY Fans 4,10 (130 [50 Hz], 150-210, 230A-315A,
330A/B-420A/B)
EXV.B 0-100% EXV % OPEN
CLR.P ON/OFF COOLER PUMP RELAY
RMT.A ON/OFF REMOTE ALARM RELAY
COMP
ENTER
CC.A1 ON/OFF COMPRESSOR A1 RELAY
CC.A2 ON/OFF COMPRESSOR A2 RELAY
CC.A3 ON/OFF COMPRESSOR A3 RELAY
CC.A4 ON/OFF COMPRESSOR A4 RELAY
UL.A1 ON/OFF UNLOADER A1 RELAY
UL.A2 ON/OFF UNLOADER A2 RELAY
HGBP ON/OFF HOT GAS BYPASS RELAY
CC.B1 ON/OFF COMPRESSOR B1 RELAY
CC.B2 ON/OFF COMPRESSOR B2 RELAY
CC.B3 ON/OFF COMPRESSOR B3 RELAY
CC.B4 ON/OFF COMPRESSOR B4 RELAY
UL.B1 ON/OFF UNLOADER B1 RELAY
UL.B2 ON/OFF UNLOADER B2 RELAY
LEGEND
EXV — Electronic Expansion Valve
32