Table 25 Configuring Temperature Reset
MODE
GREEN LED)
KEYPAD
ENTRY
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
ITEM
EXPANSION
COMMENT
CONFIGURATION
ENTER
DISP
ENTER
TEST ON/OFF TEST DISPLAY LEDs
UNIT
ENTER
TYPE X UNIT TYPE
OPT1
ENTER
FLUD X COOLER FLUID
OPT2
ENTER
CTRL X CONTROL METHOD
RSET
ENTER
CRST X COOLING RESET TYPE 0 = No Reset
1 = 4 to 20 mA Input (EMM required)
(Connect to EMM J6-2,5)
2 = Outdoor-Air Temperature
(Connect to TB5-7,8)
3 = Return Fluid (Connect to TB5-5,6)
4 = Space Temperature
CRT1 XXX.X F NO COOL RESET TEMP
Default: 125 F (51.7 C)
Range: 0 to125 F
Set to 4.0 for CRST= 1
CRT2 XXX.X F FULL COOL RESET TEMP
Default: F (−17.8 C)
Range: 0 to 125 F
Set to 20.0 for CRST=1
DGRC XX.X °F DEGREES COOL RESET
Default: F (0° C)
Range: −30 to 30° F (−16.7 to 16.7 C)
The following are examples of outdoor air and space tem-
perature resets:
LEGEND
LWT Leaving Water (Fluid) Temperature
LEGEND
LWT Leaving Water (Fluid) Temperature
44