CIRCB AN (Circuit B Analog Parameters)
DESCRIPTION STATUS UNITS POINT FORCEABLE
1 Circuit B Analog Values
2 Percent Total Capacity 0-100 % CAPB T
N
3 Percent Available Cap 0-100 % CAPB A
N
4 Discharge Pressure nnn.n PSI DP B
N
5 Suction Pressure nnn.n PSI SP B
N
6 Saturated Condensing Tmp snnn.n °F TMP SCTB
N
7 Saturated Suction Temp snnn.n °F TMP SSTB
N
8 Compressor Suction Temp snnn.n °F CTB TMP
N
9 Suction Superheat Temp snnn.n ^F SH B
N
10 EXV % Open 0-100.0 % EXV B
N
CIRCB DO (Circuit B Discrete Parameters)
DESCRIPTION STATUS UNITS POINT FORCEABLE
1 Circuit B Discretes
2 Fan B1 Relay ON/OFF FAN B1
N
3 Fan B2 Relay ON/OFF FAN B2
N
4 Oil Pressure Switch OPEN/CLOSE OILSW B
N
5 Compressor B1 Relay ON/OFF K B1 RLY
N
6 Compressor B2 Relay ON/OFF K B2 RLY
N
7 Compressor B3 Relay ON/OFF K B3 RLY
N
8 Compressor B4 Relay ON/OFF K B4 RLY
N
9 Unloader B1 Relay ON/OFF UNL B1
N
10 Unloader B2 Relay ON/OFF UNL B2
N
11 Hot Gas Bypass Relay ON/OFF HGAS N
OPTIONS (Unit Parameters)
DESCRIPTION STATUS UNITS POINT FORCEABLE
1 UNIT Analog Values
2 Cooler Entering Fluid snnn.n °F COOL EWT
N
3 Cooler Leaving Fluid snnn.n °F COOL LWT
N
4 Temperature Reset
5 4-20 MA Reset Signal nn.n ma RST MA
N
6 Outside Air Temperature snnn.n °F OAT Y
7 Space Temperature snn.n °F SPT Y
8 Demand Limit
9 4-20 MA Demand Signal nn.n ma LMT MA
N
10 Demand Limit Switch 1 ON/OFF DMD SW1
N
11 Demand Limit Switch 2 ON/OFF DMD SW2
N
12 CCN Loadshed Signal Normal/Redline/Shed DL STAT
N
13 Pumps
14 Cooler Pump Relay ON/OFF COOL PMP
N
15 Miscellaneous
16 Dual Setpoint Switch ON/OFF DUAL IN
N
17 Cooler Flow Switch ON/OFF COOLFLOW N
18 Ice Done ON/OFF ICE N