C. Unit Start-Up (cont)
PRESS ESCAPE KEY TO DISPLAY ‘OPT1’. PRESS DOWN ARROW KEY TO DISPLAY ‘OPT2’. PRESS ENTER KEY.
RECORD CONFIGURATION INFORMATION BELOW.
OPTIONS2 (Options Configuration)
DESCRIPTION STATUS DEFAULT UNITS VALUE
Control Method 0 = Switch
1 = 7 day sched.
2 = Occupancy
3 = CCN
0
CCN Address 1 to 239 1
CCN Bus Number 0 to 239 0
CCN Baud Rate 1 = 2400
2 = 4800
3 = 9600
4 = 19,200
5 = 38,400
3
Loading Sequence Select 1 = Equal loading
2 = Staged loading
1
Lead/Lag Sequence Select 1 = Automatic
2 = Circuit A leads
3 = Circuit B leads
1
High LCW Alert Limit 2 to 60 60.0 ^F
Minutes off time 0to15 0 min
PRESS ESCAPE KEY TO DISPLAY ‘OPT2’. PRESS DOWN ARROW KEY TO DISPLAY ‘RSET’. PRESS ENTER KEY.
RECORD CONFIGURATION INFORMATION BELOW:
RESETCON (Temperature Reset and Demand Limit)
DESCRIPTION STATUS DEFAULT UNITS VALUE
COOLING RESET
Cooling Reset Type 0 = No Reset
1 = 4-20 ma input
2 = External temp-OAT
3 = Return fluid
4 = External temp-SPT
0
No Cool Reset Temp 0 to 125 0.0 °F
Full Cool Reset Temp 0 to 125 125.0 °F
Degrees Cool Reset −30 to 30 0.0 ^F
DEMAND LIMIT
Demand Limit Select 0 = None
1 = External switch input
2 = 4-20 ma input
3 = Loadshed
0
Demand Limit at 20mA 0 to 100 100 %
Loadshed Group Number 0to99 0
Loadshed Demand Delta 0to60 0 %
Maximum Loadshed Time 0 to 120 60 min
Demand Limit Switch 1 0 to 100 80 %
Demand Limit Switch 2 0 to 100 50 %
LEAD/LAG
Lead/Lag Enable Enable/Disable Disable
Master/Slave Select Slave/Master Master
Slave Address 0 to 239 0
Lead/Lag Balance Select Enable/Disable Disable
Lead/Lag Balance Delta 40 to 400 168 hours
Lag Start Delay 0 to 30 5 mins
CL-5
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
----------------------------------------------------------------------------------------