Carrier 30GX 082-358 - 3.4 - 30 GX 207-358 Dimensions

Carrier 30GX 082-358
10 pages
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10
Clearances required for operation and maintenance
Clearances required for heat exchanger tube removal. Clearances D and
E can be either on the left or on the right hand side.
Water inlet
Water outlet
Power supply
Air outlet - do not obstruct
NOTE: Refer to the certified dimensional drawings supplied with the
unit, when designing an installation.
1
2
3 - DIMENSIONS, CLEARANCES, WEIGHT DISTRIBUTION (cont’d)
3.4 - 30GX 207-358
2297
A
500
500
1830
1830
2254
B
1
1
1
1
2
2
30GX-207
30GX-227
30GX-247
30GX-267
30GX-298
30GX-328
30GX-358
1351
C1
C2
30GX A B C1 C2 Weight Weight opt. 1
(kg) (kg)
207 5994 2850 621 2662 5520 6432
227 5535 6447
247 6909 2850 621 2662 6121 7213
267 6293 7385
298 7824 2050 1036 3578 7339 8615
328 8739 1150 1951 4493 7779 8475
358 7950 8646