23
OPERATION PRESS BLOCK 3 BLOCK 1 BLOCK 2
KEY LED DISPLAY DISPLAY
Hold down the MENU button until
the LED for OUTPUTS/TESTS
lights.
Press the button to go to item
loader.
Press the button to authorise
modification of the value
associated with item 1. The
OUTPUTS/TESTS menu LED
flashes to show that modification
mode is active and the value can
be modified.
Press until the value 0100 is
displayed in block 2. The LED for
OUTPUTS/TESTS in block 3
keeps flashing to show that
modification mode is active.
Press the . button again. Loader
2 of circuit A starts and the LED
for OUTPUTS/TESTS in block 3
stops flashing.
Press the . button again. Loader
2 of circuit A stops and the LED
for OUTPUTS/TESTS in block 3
starts flashing again.
Press until the value 0010 is
displayed in block 2. The LED for
OUTPUTS/TESTS in block 3
keeps flashing.
Press the button to start loader
1 of circuit B. The LED for
OUTPUTS/TESTS in block 3
stops flashing.
4.2.9.2 - Outputs other than loaders
The test procedure is as described above.
Item 2* Status/test motor cooling valves circuit A
Item 3* Status/test motor cooling valves circuit B
Item 4* Status/test oil soleniod valves circuits A + B
Item 5* Status/test oil heater outputs circuits A + B
Item 6* Status/test oil pump outputs circuits A + B
Item 7 Fan stages status/test circuit A
Item 8 Fan stages status/test circuit B
In test mode, the or buttons in block 4
display 0001, 0010, 0100 and 1000 in succes-
sion, so as to force the various fan stages in
turn on each circuit. These items only apply to
air-cooled units.
Item 9 Alarm output status/test - Circuits A & B
In test mode, the or buttons in block 4
display 01, and 10 in succession, so as to force
each alarm output status in turn on each
circuit.
Item 1 Status/Test of loaders
These items display the status of the
compressors on circuit A or B. They can
also test them independently.
For example:
Test of loader 2 circuit A and loader 1
circuit B. The password must already
have been entered in the Configuration
menu. If not, the message “no” will be
displayed in block 2 (see section 4.2.10).
0
0
1 0001
1 0100
1 0100
1 0001
1 0010
1 0010
4.2.9 - Description of the OUTPUT/TEST menu
4.2.9.1 - General
This menu displays the status of the controller outputs. When
the machine is fully stopped (LOFF) the outputs can be
actioned for tests.
ITEM FORMAT DESCRIPTION
0b
1
b
2
b
3
b
4
Status of non accessible compressors in test mode
b
1
: Compressor A1
b
2
: Compressor A2
b
3
: Compressor B1
b
4
: Compressor B2
1* b
1
b
2
b
3
b
4
Status of loaders
b
1
: Loader 1 circuit A
b
2
: Loader 2 circuit A
b
3
: Loader 1 circuit B
b
4
: Loader 2 circuit B
2* b
1
b
2
b
3
b
4
Motor cooling valve status circuit A
b
1
: Main valve compressor A1
b
2
: Additional valve compressor A1
b
3
: Main valve compressor A2
b
4
: Additional valve compressor A2
3b
1
b
2
b
3
b
4
Motor cooling valve status circuit B
b
1
: Main valve compressor B1
b
2
: Additional valve compressor B1
b
3
: Main valve compressor B2
b
4
: Additional valve compressor B2
4b
1
b
2
b
3
b
4
Oil solenoid valve status
b
1
: Oil solenoid valve compressor A1
b
2
: Oil solenoid valve compressor A2
b
3
: Oil solenoid valve compressor B1
b
4
: Oil solenoid valve compressor B2
5b
1
b
2
Oil heater status
b
1
: Oil heater circuit A
b
2
: Oil heater circuit B
6b
1
b
2
Oil pump status
b
1
: Oil pump circuit A
b
2
: Oil pump circuit B
7b
1
b
2
b
3
b
4
Fan stages status circuit A
b
1
: Fan stage 1
b
2
: Fan stage 2
b
3
: Fan stage 3
b
4
: Fan stage 4
8b
1
b
2
b
3
b
4
Fan stages status circuit B
b
1
: Fan stage 1
b
2
: Fan stage 2
b
3
: Fan stage 3
b
4
: Fan stage 4
9b
1
b
2
Alarm outputs status
b
1
: Circuit A
b
2
: Circuit B
10* nnn EXV position circuit A
11* nnn EXV position circuit B
12* nnn Variable fan speed or condenser water valve position as % - Circuit A
13 nnn Variable fan speed as % - Circuit B
14 b
1
b
2
Evaporator and condenser pump status
15 b
1
b
2
Evaporator and heat reclaim condenser heater status
b
1
: Evaporator heater
b
2
: Heat reclaim condenser heater
16 nnn Heat reclaim condenser water valve position in %
17 b
1
b
2
b
3
b
4
Heat reclaim mode solenoid valve status
b
1
: Heat reclaim coil shutoff solenoid valve, circuit A
b
2
: Heat reclaim coil drain solenoid valve, circuit A
b
3
: Heat reclaim coil shutoff solenoid valve, circuit B
b
4
: Heat reclaim coil drain solenoid valve, circuit B
18 n Local interface test
Key:
* : This item is displayed in certain unit configurations only.
b : 0 = Open/Closed; 1 = Start/Stop
n : numerical display
Access to the tests is password controlled. The password must
first have been entered in the Configuration menu (see section
4.2.10).
To carry out a test use the or buttons to access the output
to be tested and press the A button to activate modification
mode. The Output/Test LED on the user interface starts to
flash. Enter the required test value and press to start the test.
The Output/Test LED stops flashing. Press , or to stop
the test.
"no"
1
0001