Physical data —SI
30HR,HS UNIT AND COMPRESSOR
UNIT 30HR,HS SIZE 070 080 090 100 110 120 140 160
APPROXIMATE OPERATING
WEIGHT (kg)*
HR 2159 2243 2300 2919 2982 3045 3336 3527
HS 1499 1524 1551 1978 2005 2032 2297 2347
REFRIGERANT (R-22)
OPERATING CHG (kg)†
HR 47 54 59 63 66 70 78 87
HS 6.9 6.9 6.9 9.5 9.5 9.5 12.2 12.2
COMPRESSOR 06E**
(Reciprocating,
Semi-Hermetic,
29.2 r/s)
HR
Ckt A 2150 A150 6175 A150 6175 F175 6175 A150 6175 F175 6175 F175 6299 F175 6299 F299
Ckt B 6175 6175 6175 6175 A150 6175 A150 6175 F175 6299 F175 6299 F299
HS
Ckt A 2250 A250 6275 A250 6275 F275 6275 A250 6275 F275 6275 F275 6299 F275 6299 F299
Ckt B 6275 6275 6275 6275 A250 6275 A250 6275 F275 6299 F275 6299 F299
Capacity Control Steps
(see page 31)
66688888
Circuit Split, % Capacity
Ckt A 57 62.5 67 50 55 50 50 50
Ckt B 43 37.5 33 50 45 50 50 50
CONDENSER PART NO. 09RP---
HR
Ckt A 043 054 070 054 070 070 070 084
Ckt B 033 033 033 054 054 070 070 084
REFRIGERANT CONN. (in. ODM)
Liquid Line
HS
Ckt A
7
8
1
1
8
1
1
8
1
1
8
1
1
8
1
1
8
1
1
8
1
1
8
Ckt B
7
8
7
8
7
8
1
1
8
1
1
8
1
1
8
1
1
8
1
1
8
Discharge Line
Ckt A 1
5
8
1
5
8
2
1
8
1
5
8
2
1
8
2
1
8
2
1
8
2
1
8
Ckt B 1
3
8
1
3
8
1
3
8
1
5
8
1
5
8
2
1
8
2
1
8
2
1
8
LEGEND
ODM Outside Diameter Male
*Includes refrigerant operating charge.
†The 30HR unit is shipped with full operating charge; 30HS unit is shipped with holding charge only
(cooler operating charge shown condenser and interconnecting piping charge must be added for
total system charge).
**Prefix (no. of unloaders): A, F = none; 2, 6 = one.