Multiple chiller installation
NOTE: If the walls are higher than 2 m, contact the factory.
2000
1000
2000
1000
20002000
1000
1000
1000
Solid surface
Solid surface
30RA 200-240
Legend:
All dimensions are given in mm
Control box
Water inlet
Water outlet
Required clearances for air flow
Recommended clearances for maintenance
Air outlet, do not obstruct
Power cable entry
NOTE:
A Non-certified drawings.
Refer to the certified dimensional drawings supplied with the unit or
available on request, when designing an installation.
For the location of fixing points, weight distribution and coordinates of
the centre of gravity refer to the certified dimensional drawings.
B In multiple-chiller installations (maximum four units), the side clearance
between the units should be increased from 1000 to 2000 mm.
C The height of the solid surface must not exceed 2 m.