APPENDIX A
AIR CONDITIONER AND HEAT PUMP
WITH PURON ® -- QUICK REFERENCE
GUIDE
• Puron@ (R-410A) refrigerant operates at 50 percent to
70 percent higher pressures than R-22. Be sure that
servicing equipment and replacement components are
designed to operate with Puron@.
• Puron@ refrigerant cylinders are rose colored.
• Recovery cylinder service pressure rating must be 400
psig, DOT 4BA400 or DOT BW400.
• Puron@ systems should be charged with liquid
refrigerant. Use a commercial type metering device in
the manifold hose when charging into suction line with
compressor operating.
• Manifold sets should be 700 psig high side and 180 psig
low side with 550 psig low-side retard.
• Use hoses with 700 psig service pressure rating.
• Leak detectors should be designed to detect HFC
refrigerant.
• Puron@, as with other HFCs, is only compatible with
POE oils.
• Vacuum pumps will not remove moisture from oil.
• Use only factory specified liquid-line filter driers with
rated working pressures greater than 600 psig.
• Do not install a suction-line filter drier in liquid-line.
• POE oils absorb moisture rapidly. Do not expose oil to
atmosphere.
• POE oils may cause damage to certain plastics and
roofing materials.
• Wrap all filter driers and service valves with wet cloth
when brazing.
• A factory approved, liquid-line filter drier is required on
every unit.
• Do not use an R-22 TXV.
• If indoor unit is equipped with a TXV, it must be
changed to a Puron@ TXV.
• Never open system to atmosphere while it is under a
vacuum.
• When system must be opened for service, recover
refrigerant, break vacuum with dry nitrogen before
opening system.
• Always replace filter drier after opening system for
service.
• Do not vent Puron@ into the atmosphere.
• Do not use capillary tube coils.
• Observe all warnings, cautions, and bold text.
• All Puron@ heat pumps must have indoor TXV.
• Do not leave Puron@ suction line driers in place for
more than 72 hours.
APPENDIX B
WIRING DIAGRAM LIST
38AUQ
Size Electrical Characteristics Diagram Number
*07 208/260-3-60 38AU500363
460-6-60 38AU500662
575-6-60 38AU500465
*08 208/260-3-60 38AU500363
460-6-60 38AU500662
575-6-60 38AU500465
"12 208/260-3-60 38AU500363
460-6-60 38AU500662
575-6-60 38AU500465
37