Table 1A -- Physical Data -- 38AUQ*07-12 Units -- 60 Hz English
UNIT SIZE 38AUQ*
NOMINAL CAPACITY (tons)
OPERATING WEIGHTS (Ib)
Aluminum-Fin Coils
REFRIGERANT TYPE $
Operating Charge, Typical (Ib)t
Shipping Charge (Ib)
COMPRESSOR
Qty._Type
OUTDOOR FANS
Qty...Rpm
Motor Hp
Diameter (in)
Nominal Airflow (Cfm Total)
Watts (Total)
07 08 12
6 7.5 10
444 483 575
R-410A
=
18.0 21.0 I 27.0
9.0 9.0 I 9.0
1...Scroll 1...Scroll 1...Scroll
2...1100
1/4
22
6,000
610
2...1100
1/4
22
6,000
610
2...1100
1/4
22
6,000
610
OUTDOOR COIL (Oty)
Face Area (sq ft total) 17.5
Rows/Fins per inch (FPI) 2/17
CONTROLS
Pressurestat Settings (psig)
High Cutout 630 _+10
Cut-in 505 _+20
Low Cutout 27 _+3
Cut-in 44 _+5
PIPING CONNECTIONS (in. ODS)
Qty._Vapor 1...11/8
Qty._Liquid 1...3/8
LEGEND
ODS -- Outside Diameter Sweat (socket)
$ Unit isfactory-supplied with partial charge only.
1-Typical operating charge with 25 ft of interconnecting piping.
1...Round Tube/Plate Fin (RTPF)
23.0 I 28.1
2/17 2/17
630 _+10
505 _+20
27 _+3
44 _+5
1 ...11/8
1...1/2
I
630 _+10
505 _+20
27 _+3
44 _+5
1...13/8
1...1/2