28
Heat pump heating performance continued
NOTE: When the required data fall between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.
* The Btuh heating capacity values shown are net integrated values from which the defrost effect has been subtracted. The Btuh heating from supplement
heaters should be added to those values to obtain total system capacity.
The kW values include the compressor, outdoor fan motor, and indoor blower motor. The kW from supplement heaters should be added to these values to
obtain total system kilowatts.
EDB Entering Dry Bulb
INDOOR
AIR
OUTDOOR COIL ENTERING AIR TEMPERATURES
°F
3 7 17 27 37 47 57 67
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
Capacity
MBtuh
Total
Power
EDB CFM Total Integ* kW Total Integ* kW Total Integ* kW Total Integ* kW Total Integ* kW Total Integ* kW Total Integ* kW Total Integ* kW
38BYC060-33, 34 Outdoor Section With 40FK(A,B)/FK4(C,D)NF006 Indoor Section
65
1750 28.2 26.0 4.20 33.5 30.8 4.37 39.1 35.7 4.55 45.3 40.2 4.75 52.5 47.8 5.00 60.7 60.7 5.30 70.1 70.1 5.69 79.6 79.6 6.03
2000 28.6 26.3 4.22 33.8 31.1 4.38 39.5 36.0 4.54 45.7 40.6 4.72 53.0 48.3 4.95 61.3 61.3 5.23 70.7 70.7 5.56 79.4 79.4 5.87
2250 28.9 26.6 4.26 34.1 31.3 4.40 39.9 36.3 4.55 46.1 41.0 4.72 53.5 48.7 4.93 61.8 61.8 5.20 70.8 70.8 5.48 78.5 78.5 5.75
70
1750 27.8 25.5 4.38 33.2 30.5 4.59 38.8 35.4 4.78 44.9 39.8 4.99 52.0 47.3 5.25 60.0 60.0 5.57 69.3 69.3 5.97 79.7 79.7 6.41
2000 28.1 25.9 4.41 33.5 30.8 4.59 39.2 35.7 4.77 45.3 40.2 4.96 52.5 47.8 5.20 60.6 60.6 5.49 70.1 70.1 5.87 79.2 79.2 6.18
2250 28.5 26.2 4.45 33.8 31.1 4.61 39.5 36.0 4.78 45.7 40.6 4.95 52.9 48.2 5.18 61.1 61.1 5.45 70.4 70.4 5.77 78.5 78.5 6.05
75
1750 27.2 25.0 4.57 32.9 30.2 4.80 38.5 35.1 5.02 44.4 39.5 5.24 51.4 46.8 5.52 59.3 59.3 5.84 68.5 68.5 6.26 79.0 79.0 6.80
2000 27.6 25.4 4.59 33.2 30.5 4.81 38.8 35.4 5.00 44.9 39.8 5.21 52.0 47.3 5.45 60.0 60.0 5.76 69.3 69.3 6.15 79.4 79.4 6.55
2250 28.0 25.7 4.63 33.5 30.8 4.83 39.2 35.7 5.01 45.2 40.2 5.20 52.4 47.7 5.43 60.4 60.4 5.71 69.9 69.9 6.09 78.8 78.8 6.39
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section Size
Heating
Indoor
Section Size
Heating
Capacity Power Capacity Power
CC5A/CD5AA 060 1.00 1.16 CK5A/CK5BT 060 1.00 1.04
CC5A/CD5AW 060 1.00 1.10 CK5A/CK5BX 060 1.00 1.03
CE3AA 060 1.00 1.09
COILS + 58CV(A,X)135-22 FURNACE
CK3BA 060 1.00 1.11 CC5A/CD5AA 060 1.00 1.15
CK5A/CK5BA 060 1.00 1.11 CC5A/CD5AW 060 1.00 1.08
CK5A/CK5BN 060 1.00 1.07 CE3AA 060 1.00 1.08
CK5A/CK5BX 060 1.00 1.07 CK3BA 060 1.00 1.04
F(A,B)4(A,B)N(F,B,C)
060 1.00 1.08 CK5A/CK5BA 060 1.00 1.04
FB4(A,B)NB 070 1.00 1.03 CK5A/CK5BT 060 1.00 1.04
FC4(B,C)N(F,B) 060 1.00 1.08 CK5A/CK5BX 060 1.00 1.03
FC4(B,C)NB 070 1.00 1.03
COILS + 58CV(A,X)155-22 FURNACE
FG3AAA 060 1.00 1.12 CC5A/CD5AA 060 1.00 1.14
40FK(A,B)/FK4(C,D)NB
006 1.00 1.00 CC5A/CD5AW 060 1.00 1.08
COILS + 58CV(A,X)110-22 FURNACE CE3AA 060 1.00 1.07
CC5A/CD5AA 060 1.00 1.15 CK3BA 060 1.00 1.03
CE3AA 060 1.00 1.07 CK5A/CK5BA 060 1.00 1.03
CK3BA 060 1.00 1.04 CK5A/CK5BT0 06 1.00 1.03
CK5A/CK5BA 060 1.00 1.04 CK5A/CK5BX 060 1.00 1.03