Carrier 38EYG - Unit Installation Procedures; Equipment Inspection and Site Preparation; Mounting Pad and Clearance Guidelines; Operating Ambient Temperature Limits

Carrier 38EYG
12 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NOTE: Avoid contact between tubing and structure
--OUTDOOR WALL_ INDOOR WAL_
_"CAULK--_ _ F LIQUID TUBE
_/_ VAPOR TUBE
t.--INSULATION --J
THROUGH THE WALL
HANGER STRAP-- k
(AROUND VAPOR _ --
TUBE_,
h
.,_--JOIST
i] _ INSULATION
#VAPOR TUBE
f
r' MIN.----II_ L LIQUIDTUBE
SUSPENSION
A94028
Fig. 2--Connecting Tubing Installation
INSTALLATION
IMPORTANT: Specifications for this unit in residential new
construction market require using the outdoor unit, indoor unit,
refrigerant robing sets, metering device, and filter &ier listed in
presale literature. There can be no deviation. Consult the Appli-
cation Guideline and Service Manual for Residential Split-System
Air Conditioners and Heat Pumps using Puron:R; Refrigerant to
obtain required unit changes for specific applications and for R-22
retrofit.
Step 1--Check Equipment and Job Site
UNPACK UNIT
Move to final location. Remove carton taking care not to damage
unit.
INSPECT EQUIPMENT
File claim with shipping company prior to installation if shipment
is damaged or incomplete. Locate unit rating plate on unit corner
panel. It contains information needed to properly install unit.
Check rating plate to be sure unit matches job specifications.
Step 2--Install On a Solid, Level Mounting Pad
If"conditions 05"local codes require the unit be attached to pad, tie
down bolts should be used and fastened through knockouts
provided in unit base pan. Refer to unit mounting patteru in Fig. 3
to determine base pan size and knockout hole location.
On rooftop applications, mount on level platform or frame. Place
unit above a load-bearing wall and isolate unit and tubing set fi'om
structure. Arrange supporting members to adequately support unit
and minimize transmission of vibration to building. Consult local
codes goveruing rooftop applications.
I
1
C
1
I
B
I
3/8"D (953) TIEDOWN
KNOCKOUTS (2) PLACES
.I
A94199
DIMENSIONS (IN.)
UNIT
SIZE
018, 024, 030
038-080
MINIMUM
MOUNTING PAD
DIMENSIONS
22-1/2 X 22-1t2
30 X 30
TIEDOWN KNOCKOUT
LOCATIONS
A B C
3-11/16 18-1/8 14-3/8
6-1/2 23-1/2 20
Fig. 3--Mounting Unit to Pad
F.,I[_
Do not allow POE lubricant to come into contact with roofing
materiah POE may deteriorate certain types of synthetic
roofing.
Roof mounted units exposed to winds above 5 mph may require
wind baffles. Consult the Application Guideline and Service
Manual for Residential Split-System Air Conditioners and Heat
Pumps using Puron'K Refrigerant for wind baffle construction.
NOTE: Unit must be level to within ± 2 ° 3/8 in.ift) per
compressor manufacturer specifications.
Step a--Clearance Requirements
When installing, allow sufficient space for airflow clearance,
wiring, refrigerant piping, and service. Allow 30-in. clearance to
smwice end of unit and 48 in. above unit. For proper airflow, a 6-in.
clearance on 1 side of unit and 12 in. on all remaining sides must
be maintained. Maintain a distance of 24 in. between units.
Position so water, snow, or ice l'rom roof or eaves cannot fall
directly on unit.
On rooftop applications, locate unit at least 6 in. above roof
surface.
Step 4--Operating Ambient
The mininmm outdoor operating ambient in cooling mode without
additional accessories is 55°F, and the maximum outdoor operat-
ing ambient in cooling mode is 125°F. The maxinmm outdoor
operating ambient in heating mode is 66°F.