37
DIAGNOSIS AND SOLUTION (CONT)
Overload current protection diagnosis and solution (F0)
Error Code F0
Malfunction decision conditions An abnormal current rise is detected by checking the specified current detection circuit.
Supposed causes
·Power supply problems
·System blockage
·PCB faulty
·Wiring mistake
·Compressor malfunction
Troubleshooting
Check  the power supply 
Check the connections and 
wires
Stop the unit
No
Yes
No
Correct the connections or 
replace the wires.
Yes
Replace the outdoor unit
Yes
Check the reactor 
No
Replace outdoor main PCB
Check for system blockage
Yes
No Clear the blockage
Check the compressor 
resistance values
Yes
No
Replace the compressor