38MAR-04SI                                                                            Specifications subject to change without notice.                                                                     13
Step 5 - Evacuate Coil And Tubing System
Refrigerant tubes and the indoor coil should be evacuated using the 
recommended 500 microns deep vacuum method. The alternate triple 
evacuation method may be used if the procedure outlined below is 
followed.
NOTE: Always break a vacuum with dry nitrogen.
Using Vacuum Pump
1. Completely tighten flare nuts A, B, C, D. Connect the manifold 
gage charge hose to a charge port of the low side service valve (see 
Fig. 18).
2. Connect the charge hose to vacuum pump. 
3. Fully open the low side of manifold gage (see Fig. 19).
4. Start the vacuum pump.
5. Evacuate using either the deep vacuum or triple evacuation method. 
6. After evacuation is complete, fully close the low side of manifold 
gage and stop the vacuum pump operation.
7. The factory charge contained in the outdoor unit is good for up to 
25 ft. (8 m) of line length. For refrigerant lines longer than 25 ft. (8 
m), add refrigerant, up to the allowable length.
8. Disconnect the charge hose from the charge connection of the low 
side service valve. 
9. Fully open service valves B and A. 
10. Securely tighten the service valve caps.
Fig. 18 — Service Valve
Fig. 19 — Manifold
Evacuation
Evacuation of the system will remove air or nitrogen (non-condensables) 
as well as moisture. A proper vacuum will assure a tight, dry system 
before charging with refrigerant. The two methods used to evacuate a 
system are the deep vacuum method and the triple vacuum method.
Deep Vacuum Method
The deep vacuum method requires a vacuum pump capable of pulling a 
vacuum of 500 microns and a vacuum gauge capable of accurately 
measuring this vacuum depth. The deep vacuum method is the most positive 
way of assuring a system is free of air and moisture (see Figure 20).
Fig. 20 — Deep Vacuum Graph
Triple Evacuation Method
The triple evacuation method should be used when vacuum pump
is not capable of pumping down to 500 microns and system does not 
contain any liquid water. Refer to Fig. 21 and proceed as follows:
1. Attach refrigeration gauges and evacuate system down to 28 in. of 
mercury and allow pump to continue operating for an additional 15 
minutes.
2. Close service valves and shut off vacuum pump.
3. Connect a nitrogen cylinder and regulator to system and flow 
nitrogen until system pressure is 2 psig.
4. Close service valve and allow system to stand for 1 hour. During 
this time, dry nitrogen will be able to diffuse throughout the system 
absorbing moisture.
5. Repeat this procedure as indicated in Fig. 21. System will then be 
free of any contaminants and water vapor.
Fig. 21 — Triple Evacuation Method
Final Tubing Check
IMPORTANT: Check to be certain factory tubing on both the 
indoor and outdoor unit has not shifted during shipment. Ensure 
tubes are not rubbing against each other or any sheet metal. Pay 
close attention to the feeder tubes, making sure wire ties on feeder 
tubes are secure and tight.
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or 
improper operation.
Never use the system compressor as a vacuum pump.
CAUTION
Outdoor Unit Indoor UnitRefrigerant
Service Valve
High side valve
Charge hose
Charge hose
Vacuum
01234567
1000
1500
LEAK IN
SYSTEM
SYSTEM TIGHT
CHECK FOR TIGHT, DRY SYSTEM
(IF IT HOLDS DEEP VACUUM)
EVACUATE
BREAK VACUUM WITH DRY NITROGEN
WAIT
EVACUATE
RELEASE CHARGE INTO SYSTEM
BREAK VACUUM WITH DRY NITROGEN
EVACUATE
WAIT