SG-38MARB-01 Specifications subject to change without notice. 35
DIAGNOSIS AND SOLUTION (CONT)
Remarks:
Use a multimeter to test the DC voltage between the 2 port (or S or L2 port) and 3 port (or N or S port) of outdoor unit.
The red pin of multimeter connects with 2 port (or S or L2 port) while the black pin is for 3 port (or N or S port) the unit is normal running,
the voltage is moving alternately as positive values and negative values
If the outdoor unit has malfunction, the voltage has always been the positive value.
While if the indoor unit has malfunction, the voltage has always been a certain value.
Use a multimeter to test the reactor’s resistance which does not connect with capacitor.
The normal value should be around zero ohm. Otherwise, the reactor must have malfunction.
S and N
or
L2 and S
or
2 and 3