Refrigerant Leakage Detection Diagnosis and Solution (EC)
Troubleshooting
Error Code EC
Malfunction decision conditions
Define the evaporator coil temp.T2 of the compressor just starts running as Tcool. In the beginning 5 minutes
after the compressor starts up, if T2 <Tcool-35.6°F(Tcool-2°C) does not keep continuous 4 seconds and this
situation happens 3 times, the display area shows “EC” and AC turns off.
Supposed Causes
•T2 sensor faulty
Indoor PCB faulty
System problems, such as leakage or blocking
Is cool air blowing from the indoor air outlet?
Yes
Power OFF.
Wait 2 minutes then restart the unit.
ŽĞƐƚŚĞƉƌŽďůĞŵƐƟůůĞdžŝƐƚ
Check the system for leaks.
Are any leaks present?
No
No
Check the system for blockages and
ŝĨĂŶLJĞdžŝƐƚĐůĞĂƌƚŚĞŵ
Check the T2
sensor.
Is it securely
ĂƩĂĐŚĞĚ
Yes
Replace the indoor PCB.
Repair the leak and recharge the refrigerant.
Yes
Yes