38MBR: Service Manual
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
38
J3 Malfunction
Troubleshooting
Error Code J3
Malfunction decision conditions
When the voltage signal that the IPM sends to the compressor is abnormal, the display LED shows “J3” and
the unit turns off.
Supposed Causes
•Faulty wiring
• Faulty IPM board
• Faulty outdoor fan assembly
• Compressor malfunction
• Faulty outdoor PCB
J3 displayed
PFC module protecƟon
Check whether the
connecƟng line
between the main
board and the PFC
module is connected
lightly.
Measure whether the
voltage between
P and N is normal.
Refer to Appendix 3.
Yes
Replace the outdoor
main board.
Yes
No
No
Replace the inductance.
Replace the PFC module.
Tighten the
connecƟon.
No
Check whether the
PFC module’s inductance is good.
If it is, the resistance of the
two ports is 0.
No
Yes
Problem solved.
Yes