38MGRBQ: Service Manual
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
71
Outdoor compressor lack phase protection (PC43)
Outdoor unit IR chip drive failure (PC45) 
 three-
phase output for obvious 
open circuit 
,then restart the unit 
2 minutes later.Is it still 
displaying the error code?
The unit operates 
normally
Check both ends of the 
compressor connecting line. 
Are the connections good?
Correct the connections
Check whether the three-
phase resistance of the 
compressor is symmetrical 
Replace the  
Yes
Yes
Yes
No
No
No
Replace the main PCB
No
Problem solved
Yes
 
2 minutes later.
Replace the i