EasyManua.ls Logo

Carrier 38VTA060 - Specifications

Carrier 38VTA060
12 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3
TABLE 1 SPECIFICATIONS
RLA : Rated Load Amps FLA : Full Load Amps LRA : Locked Rotor Amps
Notes : 1) MCA values are used for sizing the field supplied wires.
2) MOCP values are used for sizing the field supplied standard fuses or circuit breakers.
MODEL 38VTA
040 050 060
OPERATING WEIGHT kg 86 96 98
REFRIGERANT Type R-22
Factory Charged kg 1.0
COMPRESSORS Type Scroll
Oil charged (l) 1.36 1.95 1.77
LRA 50.0 65.5 74.0
RLA 7.9 10.0 10.0
Power Supply 400-3-50
CONDENSER FAN Type Propeller
Number 1
Blade dia. (mm) 609
Speed (rpm) 710
Drive Direct Drive
FAN MOTOR Type Permanent Split Capacitor
Power Supply 230-1-50
FLA 1.46
CONDENSER COIL Rows - fins/m 2 - 591
Face area (m
2
) 1.14
CONNECTIONS Type Flare
Liquid, (mm) 9.50
Suction, (mm) 19.05
POWER SOURCE (V-Ph-Hz) Nominal 400 - 3 - 50
ABSOLUTE MIN - MAX VOLTAGE (V) 360-440
MINIMUM CIRCUIT AMPS (MCA) 11.0 14.0 14.0
MAXIMUM OVERCURRENT PROTECTION (MOCP) 20 25 25
FIG. 4 WALL MOUNTINGFIG. 3 GROUNDING MOUNTING

Related product manuals