42HQE009(012)/38YE009(012)
GB
ENGLISH
1. Remove the  electric parts cover  from the outdoor
    unit.
2. Connect the connective  cables to the terminals as
    identified  with their  respective matched  numbers
    on the terminal block of  indoor and outdoor units.
3. To prevent the ingress of  water, from a loop of the
    connective  cable as  illustrated in  the  installation
    diagram of indoor and outdoor units.
4. Insulate unused cords (conductors) with PVC-tape.
    Process them  so they do not  touch any electrical
    or metal parts.
Wrong wiring connections may cause some electrical
parts to  malfunction. A  disconnection device having
an air gap contact separation in all active conductors
should be  incorporated in the fixed wiring according
to the National Wiring Regulation. All wiring must 
comply with local and national electrical codes and be 
installed by qualified and skilled electrician.
Cover
Screw
(Cooling & heating type)
Terminals on the outdoor unit
Wire-holding
board
Connective cable
CAUTION
4. WIRING CONNECTION
1
0
m
m
40m
m
1
3
4
2(N)
Oblique
90 C
Roughness
Burr
.
.
.
CAUTION
3. REFRIGERANT PIPING CONNECTION
A
1. Cut a pipe with a pipe cutter.
Align pipes to be connected.
Sufficiently tighten  the flare  nut with fingers,
and then tighten it with a spanner and torque
wrench as shown.
Excessive  torque can  break nut depending
on installation conditions.
2. Insert a flare nut into a pipe and flare the
    pipe.
Outer diam.
(mm)
A(mm)
Max.
Min.
Outer
diam.
Tightening
torque(N.cm)
Additional tightening
torque(N.cm)
6.35mm
1570
(160kgf.cm)
1960
(200kgf.cm)
2940
(300kgf.cm)
4410
(450kgf.cm)
12.7mm
6.35
1.3 0.7
12.7
1.8 1.0
1. Flaring 2. Tightening Connection
9.53mm
2940
(300kgf.cm)
3430
(350kgf.cm)
9.53
1.6
1.0