PERFORMANCE DATA (CONT.)
COOLING CAPACITIES
COOLING ONLY 38HDF036 WITH 40KMC03036
Tem p ° F (° C)
Air Entering
Condenser
(Edb)
Air Entering Evaporator --- Cfm/BF
635 / 0.05 720 / 0.05 875 / 0.05
Air Entering Evaporator --- Ewb ° F (° C)
57
(13.9)
62
(16.7)
67
(19.4)
72
(22.2)
57
(13.9)
62
(16.7)
67
(19.4)
72
(22.2)
57
(13.9)
62
(16.7)
67
(19.4)
72
(22.2)
55
(12.8)
TCG 33.0 36.3 39.7 43.0 34.8 38.1 40.9 44.6 36.6 39.8 43.2 45.7
SHG 29.7 26.9 24.1 20.9 31.8 29.1 24.6 21.8 33.9 30.9 27.0 23.0
TC 32.6 35.8 39.2 42.5 34.2 37.5 40.2 44.0 35.9 39.1 42.4 44.9
kW 2.07 2.10 2.11 2.13 2.09 2.09 2.14 2.13 2.12 2.12 2.14 2.13
CMP 1.65 1.68 1.69 1.71 1.63 1.63 1.68 1.67 1.62 1.62 1.64 1.63
LDB 38.0 42.3 46.7 51.7 40.3 44.2 50.1 54.1 45.3 48.8 53.2 57.6
LWB 34.9 40.0 45.3 51.1 36.9 42.0 47.8 53.3 40.1 45.3 50.8 56.8
65
(18.3)
TCG 32.1 35.3 38.8 42.2 33.7 36.7 40.4 43.5 35.8 39.0 42.1 45.0
SHG 29.2 26.5 23.5 20.5 31.2 28.1 24.7 21.2 34.3 30.8 26.6 22.2
TC 31.6 34.8 38.3 41.7 33.1 36.1 39.7 42.9 35.1 38.2 41.4 44.3
kW 2.30 2.33 2.35 2.36 2.31 2.34 2.36 2.37 2.33 2.35 2.36 2.39
CMP 1.87 1.91 1.92 1.94 1.85 1.88 1.90 1.91 1.83 1.85 1.86 1.89
LDB 38.6 42.9 47.6 52.2 41.1 45.4 50.1 54.8 44.9 48.8 53.5 58.5
LWB 35.7 40.7 46.0 51.6 37.7 42.9 48.1 53.9 40.5 45.8 51.3 57.1
75
(23.9)
TCG 30.9 34.1 37.6 40.9 32.4 35.6 39.1 42.5 34.9 37.5 40.8 44.0
SHG 28.6 25.9 22.9 19.9 30.5 27.6 24.2 20.8 33.4 30.1 26.0 21.8
TC 30.4 33.6 37.1 40.4 31.8 35.0 38.4 41.9 34.2 36.8 40.0 43.3
kW 2.54 2.57 2.60 2.62 2.55 2.60 2.61 2.62 2.59 2.60 2.62 2.64
CMP 2.12 2.15 2.18 2.20 2.09 2.14 2.15 2.16 2.09 2.10 2.12 2.14
LDB 39.5 43.7 48.4 53.1 42.0 46.0 50.7 55.3 45.8 49.5 54.1 58.8
LWB 36.7 41.6 46.8 52.3 38.5 43.6 48.8 54.4 41.0 46.5 51.9 57.5
85
(29.4)
TCG 29.7 32.8 36.2 39.3 31.1 34.2 37.6 41.0 33.8 36.0 39.4 42.5
SHG 27.9 25.3 22.5 18.9 29.7 27.0 23.5 20.2 32.2 29.6 25.5 21.2
TC 29.2 32.3 35.7 38.8 30.5 33.5 37.0 40.4 33.0 35.3 38.6 41.8
kW 2.81 2.84 2.89 2.90 2.82 2.86 2.89 2.91 2.86 2.89 2.90 2.92
CMP 2.38 2.42 2.46 2.48 2.36 2.40 2.43 2.45 2.36 2.39 2.40 2.42
LDB 40.5 44.6 49.0 54.5 43.0 46.8 51.5 56.1 47.1 50.1 54.7 59.4
LWB 37.6 42.6 47.6 53.3 39.4 44.5 49.7 55.1 41.6 47.2 52.5 58.1
95
(35.0)
TCG 28.2 31.3 34.7 38.2 29.8 32.6 35.9 39.4 31.9 34.4 37.2 41.1
SHG 27.0 24.6 21.7 18.7 28.7 26.3 22.9 19.5 31.9 29.1 24.2 20.9
TC 27.7 30.8 34.2 37.7 29.2 32.0 35.3 38.8 31.1 33.7 36.4 40.4
kW 3.10 3.13 3.20 3.21 3.11 3.15 3.21 3.22 3.15 3.19 3.31 3.32
CMP 2.67 2.71 2.77 2.79 2.65 2.69 2.75 2.76 2.65 2.69 2.81 2.82
LDB 41.7 45.6 50.1 54.8 44.2 47.6 52.2 56.9 47.4 50.6 55.5 59.7
LWB 38.8 43.7 48.7 54.0 40.3 45.5 50.6 55.9 42.6 48.0 53.2 58.6
105
(40.6)
TCG 26.8 29.6 33.0 36.4 28.1 30.8 34.2 37.4 30.5 32.5 35.9 39.2
SHG 26.1 23.8 20.9 17.7 28.1 25.5 22.3 18.4 30.5 28.3 24.0 20.1
TC 26.3 29.1 32.5 35.9 27.5 30.2 33.6 36.7 29.7 31.8 35.2 38.5
kW 3.41 3.45 3.52 3.55 3.43 3.47 3.55 3.55 3.48 3.51 3.54 3.57
CMP 2.98 3.02 3.09 3.12 2.97 3.01 3.09 3.09 2.98 3.01 3.04 3.07
LDB 43.1 46.6 51.1 56.1 45.0 48.6 53.0 58.3 48.9 51.4 56.2 60.6
LWB 39.9 44.9 49.7 55.0 41.4 46.5 51.5 56.9 43.3 48.9 54.0 59.3
115
(46.1)
TCG 25.1 27.6 31.0 34.5 26.6 28.8 32.2 35.6 28.9 30.4 33.8 37.2
SHG 25.1 23.0 20.1 17.0 26.6 24.7 21.4 17.9 28.9 27.5 23.3 19.4
TC 24.6 27.1 30.5 34.0 26.0 28.2 31.6 35.0 28.1 29.7 33.1 36.4
kW 3.75 3.79 3.87 3.91 3.77 3.81 3.90 3.92 3.83 3.86 3.91 3.94
CMP 3.32 3.36 3.44 3.48 3.31 3.35 3.44 3.46 3.33 3.36 3.41 3.44
LDB 44.5 47.8 52.3 57.1 46.9 49.6 54.1 58.9 50.5 52.2 56.9 61.2
LWB 41.1 46.2 51.0 56.1 42.3 47.7 52.6 57.7 44.2 49.8 54.8 60.1
125
(51.7)
TCG 23.6 25.5 28.8 32.2 25.0 26.5 29.9 33.4 27.2 28.0 31.4 34.7
SHG 23.6 22.1 19.2 16.1 25.0 23.8 20.5 17.2 27.2 26.3 22.4 18.5
TC 23.1 25.0 28.3 31.7 24.4 25.9 29.3 32.7 26.4 27.3 30.7 33.9
kW 4.12 4.15 4.25 4.30 4.15 4.18 4.28 4.32 4.21 4.23 4.30 4.33
CMP 3.70 3.73 3.82 3.87 3.69 3.72 3.82 3.86 3.71 3.73 3.80 3.83
LDB 46.7 49.1 53.6 58.4 48.9 50.7 55.3 59.7 52.3 53.5 57.8 62.1
LWB 42.3 47.6 52.3 57.3 43.4 49.0 53.8 58.8 45.0 50.9 55.8 61.0
Rating condition
LEGEND
BF --- Bypass Factor
CMP --- Compressor
Edb --- Entering Dry Bulb
Ewb --- Entering Wet Bulb
k W --- To ta l Po we r
LDB --- Leaving Dry Bulb
L W B --- L e a v i n g W e t B u l b
SHG --- Gross Sensible Ca pacity (1000 Btu/hour)
TC --- Total Net Cool ing Capacity (1000 Btu/hour)
TCG
---
Gross
Cooling
Capacity
Btu/hour)
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. Th e SHG is based on 80_F (26.67_C) edb temperature of air
entering indoor coil.
Below 80_F (26.67_C) edb, subtract (corr factor x cfm) from
SHG.
Above 80_F (26.67_C) edb, add (corr factor x cfm) to SHG.
Correction Factor = 1.10 x (1 --- BF) x (edb --- 80).