16
PERFORMANCE DATA (CONT.)
COOLING CAPACITIES
HEAT / COOL 38HDF018 WITH 40KMQ01824
Tem p ° F (° C)
Air Entering
Condenser
(Edb)
Air Entering Evaporator --- Cfm/BF
445 / 0.05 530 / 0.05 680 / 0.05
Air Entering Evaporator --- Ewb ° F (° C)
57
(13.9)
62
(16.7)
67
(19.4)
72
(22.2)
57
(13.9)
62
(16.7)
67
(19.4)
72
(22.2)
57
(13.9)
62
(16.7)
67
(19.4)
72
(22.2)
55
(12.8)
TCG 17.0 18.0 19.4 20.6 17.8 19.0 20.0 21.1 18.9 19.7 20.7 21.4
SHG 14.7 13.6 11.9 10.1 15.5 15.0 12.5 10.5 18.9 15.7 13.3 10.9
TC 16.7 17.7 19.2 20.4 17.4 18.7 19.7 20.7 18.5 19.3 20.3 21.0
kW 1.01 1.00 1.01 1.01 1.00 1.00 1.02 1.00 1.00 1.01 1.01 1.00
CMP 0.80 0.79 0.80 0.80 0.77 0.77 0.79 0.77 0.74 0.75 0.75 0.74
LDB 50.3 52.9 56.6 60.6 53.8 55.0 59.5 63.1 55.1 59.7 63.0 66.5
LWB 41.7 47.4 52.9 58.7 43.8 49.3 55.1 60.9 46.3 52.1 57.7 63.5
65
(18.3)
TCG 16.7 17.4 19.1 20.2 17.2 18.2 19.7 20.7 18.8 19.0 20.3 21.2
SHG 14.8 13.5 11.9 9.9 17.2 14.4 12.5 10.4 18.8 15.6 13.3 11.0
TC 16.5 17.2 18.9 20.0 16.9 17.9 19.3 20.4 18.3 18.6 19.9 20.8
kW 1.12 1.12 1.12 1.13 1.11 1.13 1.13 1.13 1.11 1.12 1.13 1.12
CMP 0.91 0.91 0.91 0.92 0.88 0.90 0.90 0.90 0.85 0.86 0.87 0.86
LDB 50.1 53.1 56.5 60.9 50.7 55.9 59.5 63.3 55.3 59.8 63.0 66.3
LWB 41.9 48.0 53.2 59.0 44.3 49.9 55.3 61.1 46.4 52.5 57.9 63.6
75
(23.9)
TCG 15.7 17.1 18.3 19.7 16.8 17.5 19.1 20.2 18.2 18.4 19.7 20.7
SHG 15.7 13.7 11.6 9.8 16.8 14.1 12.5 10.2 18.2 15.5 13.3 10.9
TC 15.5 16.9 18.1 19.4 16.5 17.2 18.8 19.9 17.8 17.9 19.3 20.2
kW 1.25 1.25 1.26 1.26 1.25 1.26 1.25 1.26 1.25 1.26 1.26 1.25
CMP 1.04 1.04 1.05 1.05 1.02 1.03 1.02 1.03 0.99 1.00 1.00 0.99
LDB 48.2 52.6 57.3 61.2 51.5 56.4 59.4 63.6 56.0 59.9 63.1 66.5
LWB 43.0 48.2 53.8 59.4 44.6 50.5 55.7 61.4 46.8 52.8 58.2 63.8
85
(29.4)
TCG 15.2 16.5 17.6 19.0 16.2 17.0 18.3 19.6 17.6 17.7 19.1 20.1
SHG 15.2 13.5 11.3 9.5 16.2 14.4 12.1 10.0 17.6 15.2 13.1 10.6
TC 15.0 16.2 17.3 18.8 15.8 16.7 18.0 19.2 17.2 17.3 18.7 19.6
kW 1.39 1.40 1.40 1.40 1.40 1.40 1.40 1.41 1.40 1.40 1.40 1.41
CMP 1.18 1.19 1.19 1.19 1.17 1.17 1.17 1.18 1.14 1.14 1.14 1.15
LDB 49.1 52.9 57.9 61.7 52.6 55.9 60.1 64.0 56.8 60.3 63.3 66.8
LWB 43.5 48.8 54.4 59.9 45.2 50.8 56.2 61.8 47.2 53.2 58.5 64.1
95
(35.0)
TCG 14.6 15.7 16.8 18.3 15.5 16.2 17.5 18.8 16.9 17.1 17.4 19.3
SHG 14.6 13.4 11.0 9.2 15.5 14.1 11.9 9.7 16.9 14.9 12.4 10.4
TC 14.3 15.4 16.5 18.1 15.2 15.9 17.2 18.5 16.5 16.6 17.0 18.9
kW 1.55 1.56 1.56 1.56 1.56 1.56 1.56 1.57 1.56 1.56 1.55 1.57
CMP 1.34 1.35 1.35 1.35 1.33 1.33 1.33 1.34 1.30 1.30 1.29 1.31
LDB 50.5 53.2 58.4 62.3 53.7 56.4 60.4 64.4 57.7 60.7 63.3 67.1
LWB 44.1 49.5 55.1 60.4 45.7 51.4 56.8 62.2 47.6 53.5 58.9 64.4
105
(40.6)
TCG 13.8 14.8 15.8 17.3 14.8 15.5 16.5 18.0 16.2 16.3 17.2 18.5
SHG 13.8 12.9 10.5 8.7 14.8 13.4 11.5 9.4 16.2 13.4 12.6 10.1
TC 13.6 14.5 15.6 17.1 14.4 15.2 16.2 17.7 15.7 15.9 16.8 18.0
kW 1.72 1.73 1.74 1.74 1.73 1.73 1.74 1.74 1.74 1.74 1.74 1.74
CMP 1.51 1.52 1.53 1.53 1.50 1.50 1.51 1.51 1.48 1.48 1.48 1.48
LDB 52.0 54.2 59.4 63.4 55.0 57.6 61.1 64.9 58.8 62.7 63.9 67.5
LWB 44.9 50.3 55.9 61.2 46.3 51.9 57.4 62.7 48.1 53.9 59.4 64.8
115
(46.1)
TCG 13.1 13.9 15.0 16.4 13.9 13.9 15.4 16.9 15.2 15.0 16.1 17.4
SHG 13.1 12.2 10.3 8.5 13.9 13.9 11.1 9.0 15.2 15.0 12.4 9.7
TC 12.8 13.7 14.7 16.1 13.5 13.6 15.0 16.5 14.8 14.6 15.7 17.0
kW 1.90 1.91 1.92 1.93 1.91 1.91 1.93 1.93 1.93 1.93 1.93 1.93
CMP 1.69 1.70 1.71 1.72 1.68 1.68 1.70 1.70 1.67 1.67 1.67 1.67
LDB 53.6 55.7 59.7 63.7 56.6 56.7 61.7 65.6 60.0 60.4 64.2 68.0
LWB 45.7 51.1 56.5 61.8 47.0 52.6 58.2 63.4 48.6 54.6 59.9 65.2
125
(51.7)
TCG 12.1 12.1 13.7 15.0 12.9 12.9 14.1 15.6 14.2 13.9 14.8 16.0
SHG 12.1 12.1 10.0 8.1 12.9 12.9 10.7 8.6 14.2 13.9 12.2 9.2
TC 11.9 11.9 13.5 14.8 12.6 12.6 13.8 15.3 13.7 13.5 14.3 15.6
kW 2.09 2.09 2.12 2.13 2.11 2.10 2.12 2.13 2.13 2.13 2.13 2.13
CMP 1.88 1.88 1.91 1.92 1.88 1.87 1.89 1.90 1.87 1.87 1.87 1.87
LDB 55.5 55.6 60.2 64.6 58.3 58.4 62.4 66.3 61.5 61.9 64.4 68.6
LWB 46.6 52.6 57.5 62.7 47.8 53.8 58.9 64.1 49.3 55.2 60.6 65.8
Rating condition
Not recommended for long---term operation.
LEGEND
BF --- Bypass Factor
CMP --- Compressor
Edb --- Entering Dry Bulb
Ewb --- Entering Wet Bulb
k W --- To ta l Po we r
LDB --- Leaving Dry Bulb
L W B --- L e a v i n g W e t B u l b
SHG --- Gross Sensible Ca pacity (1000 Btu/hour)
TC --- Total Net Cool ing Capacity (1000 Btu/hour )
TCG --- Gross C ooling C a pacity (1000 Btu/hour)
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. Th e SHG is based on 80_F (26.67_C) edb temperature of air
entering indoor coil.
Below 80_F (26.67_C) edb, subtract (corr factor x cfm) from SHG.
Above 80_F (26.67_C) edb, add (corr factor x cfm) to SHG.
Correction Factor = 1.10 x (1 --- BF) x (edb --- 80).
0KMC, KMQ / 38HDF, QR