Ductless Start-Up Checklist (CONT)
Piping
Leak Check:
System held 500 psig (max. 550psi) for a minimum of 30 minutes using dry nitrogen. YES:______ NO:______
Evacuation Method:
Was the Triple Evacuation Method used as outlined in the installation manual? YES:______ NO:______
Was the Deep Vacuum Method used as outlined in the installation manual? YES:______ NO:_______
Did the System Hold 500 microns for 1 hour? YES:______ NO:_______
Does the line set match the diameter of the evaporator connections? YES:______ NO:_______
For Conventional Fan Coils, does the line set match the outdoor unit size? YES:______ NO:_______
Single Zone Piping:
Has the liquid pipe length been measured and the additional charge calculated? Size:___________ Length:_________ Charge:____________
Performance Check
NOTE:
T1 - Ambient Space Temperature Sensor
T2 - IDU Coil Temperature Sensor
T3 - Outdoor Coil Temperature Sensor
T4 - Outdoor Ambient Temperature
Tb - Suction Line Temperature @PMV
Tp - Discharge Temperature Sensor
Th - IPM Board Temperature
LA/Lr - PMV Temperature
Error Codes
Were there any error codes present at start-up? YES:______ NO:______
Comments:
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________
NOTES:
PORT LIQUID SIZE SUCTION SIZE LENGTH CHARGE
NOTES:____________________________________
___________________________________________
___________________________________________
A
For 1:1 Single Zone Systems: Adjust the set-point to create an operational call for the desired testing operation. Allow the system to run for a
minimum of 10 min. and record the following details:
(Operational data recorded on applicable heads with the wireless remote controller’s Point Check function)
UNIT
SET-POINT
MODE T1 T2 T3 T4 Tb Tp Th LA/Lr
A
Indoor Unit Error Code: Notes:
Outdoor Unit Error Code:
Wall Controller:
24V Interface: