E3(Communication malfunction between IPM board and outdoor main board) error
diagnosis
Error Code E3
Malfunction decision conditions PCB main chip does not receive feedback from IPM module during 60 seconds.
Supposed causes
S Wiring mistake
S PCB faulty
Troubleshooting
Communication malfunction between 
IPM board and outdoor main board
Is there at least one LED in 
the IPM board light?
Check the signal wire between 
the IPM module and the main 
board, is it connected good?
Reconnect and retry. Is
error still display?
Replace IPM board, and
then check whether the 
system can run normally 
Replace the electric control 
box
No
No
No
No
Yes
Trouble is solved
No
Yes
Replace outdoor main 
board, and then check 
whether the system can run 
normally
No
Yes
Yes