48
E6(PFC module protection) error diagnosis and
solution.
Error Code E6
Malfunction decision conditions
When the voltage signal that PFC sends to main control board is abnormal, the display LED
displays “E6” and the AC turns off.
Supposed causes
S Wiring mistake
S Outdoor PCB faulty
S Inductance of PFC module faulty
S PFC module malfunction
Troubleshooting
PFC module protection
Check whether the 
connecting line between 
main board and the PFC 
module is connected tightly
Yes
Check whether the voltage 
range of P-N on IPM 
module is normal? DC277-
356V for 18-27KBtu/h;
DC277-410V for 36KBtu/h
No
Check whether the 
inductance of PFC module 
is good? If the inductance is 
good, the resistance of the 
two ports is 0
Yes
Replace the inductance
No
Connect it tightly, check
normal or not
Replace the outdoor main board
Yes
Yes
No
No
Replace the PFC module
Trouble is solved