E1, E2 (Communication malfunction between indoor and outdoor units) error diagnosis and
solution.
Error Code E2
Malfunction decision conditions
Indoor unit does not receive the feedback from outdoor unit during 120 seconds or outdoor
unit does not receive the feedback from any one indoor unit during 180 seconds.
Supposed Causes
S Wiring mistake
S Indoor or outdoor PCB faulty
Troubleshooting
Communicaon malfuncon between indoor and 
outdoor units
Start: Power off , then Power on the 
A/C by the Breaker. (reconnect the 
power wire). Is it sll displaying the 
error code?
Yes
No
Change outdoor unit PCB assembly(include 
wiring) totally
Check wiring on the outdoor and indoor 
terminal follow the wiring diagram. Is all 
connecng correctly?
Yes
No
Measure Vs, is it moving 
alternately between posive value 
and negave value? (Vs is the 
voltage between S and L2). Refer 
PIC 1
Turn on all indoor unit by remote 
controller. Is all indoor unit display
Turn off the all indoor units. Is IPM 
power LED or operang
 LED  lamp 
On? Refer PIC2
Yes
A: 
Is all the wiring between 
terminal and Indoor PCB 
connect ok?
No
Yes
A
No
Reconnect the wiring
Is indoor units number correct? Check 
on the outdoor check point . (2 for dual 
zone, 3 for tri zone, 4 for qua zone). 
Refer PIC 4.
Yes
No first me
Yes
Yes
Change the Indoor PCB
Power on by remote 
controller, I
Is it sll 
displaying the error code
 
aer 3 minutes?
Trouble is solved
No second me
No
Yes
Reconnect the wiring
No
change IPM
No
Is the reactor connecng 
well˛
No Reconnect the wiring
Change Outdoor Main PCB
Yes
No
Is main boardĀ ā 
lamp on? Refer PIC 3.