P4(Temperature protection of compressor discharge) error diagnosis and
solution.
Error Code P4
Malfunction decision conditions
When the compressor discharge temperature(T5) is more than 239_F for 10 seconds, the
compressor stops and restarts when T5 is less than 194
_F.
Supposed causes
S Refrigerant leakage
S Wiring mistake
S The discharge temperature sensor faulty
S Outdoor PCB faulty
Troubleshooting
 
ompressor disc
arge
compressor discharge 
C
ec
 w
et
er t
e
compressor disc
arge tem
 
s 
ore t
an 
15
C 
Check whether the 
compressor discharge temp. is 
more than 239°F ?
heck whether the
connect
on
r
t
etween 
compressor
sc
arg
tem
n
B
ccor
ng 
to w
r
ng 
agram
Check whether the 
connection is right between 
compressor discharge temp.
sensor and PCB according 
to wiring diagrams?
asure t
e res
stance va
ue 
 compressor discharge 
tem
ensor
f the value is
ot norma
s 
orma
re
er to 
e Appen
ix
Measure the resistance value 
of compressor discharge 
temp. sensor. If the value is 
not normal is normal refer to 
the Appendix 2?
No
Yes
Yes
No
Correct the wiring connection
Stop leaking and add re
rigeran
Stop leaking and add refrigerant
ep
ace t
e compressor 
sc
arge temp
ensor
Replace the compressor discharge temp. sensor
No
Yes
ep
ace 
g
 pressure va
ve ass
Replace high pressure valve assy
Yes
No
p
ace out
oor ma
nP
B
Replace outdoor main PCB
No
Check whether the 
refrigerant is leak