E4 (open or short circuit of outdoor temperature sensor) diagnosis and solution F1/F2/F3/F4/F5 (open or short circuit of indoor
coil
temperature sensor) diagnosis and
solution.
Error Code E4/F1/F2/F3/F4/F5
Malfunction decision conditions If the sampling voltage is lower than 0.06V or higher than 4.94V, the LED displays the failure.
Supposed causes
S Wiring mistake
S Sensor faulty
S PCB faulty
Troubleshooting
Check the connections 
between temperature 
sensor and PCB. Are
the connections good?
Correct the connections.
No
Yes
Yes Replace indoor or outdoor PCB.
Replace the sensor 
Check the resistance value 
of the sensor via Appendix 1
and Appendix 2
Is it normal?
No