EasyManua.ls Logo

Carrier 40MBC/38MAQ - Troubleshooting

Carrier 40MBC/38MAQ
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
19
TROUBLESHOOTING
For ease of service, the systems are equipped with diagnostic code
display LEDs on both the indoor and outdoor units. The outdoor
diagnostic display consists of two LEDs (Red and Green) on the
outdoor unit board and is limited to a few errors. The indoor
diagnostic display is a combination of flashing LEDs on the
display panel or the front of the unit. If possible, always check the
diagnostic codes displayed on the indoor unit first.
The diagnostic codes displayed in the indoor and outdoor units are
listed in the tables below.
INDOOR UNIT DIAGNOSTIC GUIDES
Table 7—Indoor Unit Diagnostic Guides
Operation Lamp Timer Lamp Display LED Status
1time
X E0 Indoor unit EEPROM error
2times X E1 Communication malfunction between indoor and outdoor units
4times X E3 Indoor fan speed has been out of control
5times X E4 Indoor room temperature sensor T1 open circuit or short circuit
6times X E5 Evaporator coil temperature sensor T2 open circuit or short circuit
7times X EC Refrigerant leakage detection
8times X EE Water --- level alarm malfunction
1time O F0 Current overload protection
2times O F1 Open circuit or short circuit of outdoor ambient temperature sensor T4
3times O F2 Open circuit or short circuit of condenser coil temperature sensor T3
4times O F3 Open circuit or short circuit of Compressor discharge temperature sensor T5
5times O F4 Outdoor unit EEPROM error
6times O F5 Outdoor fan speed has been out of control
7times O F6 T2B sensor error
8times O F7 Lifting---panel communication error
9times O F8 Lifting--- panel malfunction
10 times O F9 Lifting --- panel is not closed
1time P0 IPM malfunction
2times P1 Over voltage or over low voltage protection
3times P2 High temperature protection of compressor top
4times P3 Outdoor low temperature protection
5times P4 Inverter compressor drive error
6times P5 Mode conflict
7times P6 Compressor low--- pressure protection
8times P7 Outdoor IGBT temperature sensor error
O (light) X (off) (flash)
For additional diagnostic information, refer to the Service Manual.
OUTDOOR UNIT DIAGNOSTIC GUIDES
Ta ble 8—Outdoor Unit Diagnostic Guides
LED2 LED1 Indoor Unit display Failure Mode
(Green) (Red)
O X St a ndby, nor m a l
X O Operation, normal
O E5 Compressor drive board EEPROM error
X P0 IPM malfunction or IGBT over--- strong current protection
O O P1 Over voltage or too low voltage protection
X P4 Inverter compressor drive error
O P4 Inverter compresso r drive error
P4 Comm uni c ati o n malfunct i on between main contro l board and driver board
= Flashing, X = Off
For additional diagnostic information, refer to the Service Manual

Related product manuals