DIAGNOSIS AND SOLUTION (CONT)
P0 (IPM malfunction or IGBT over−strong current protection diagnosis and solution)
Description: When the voltage signal the IPM sends to the compressor drive chip is abnormal, the display LED displays “P0” and the air
conditioner turns off.
Recommended parts to prepare:
S Wiring mistake
S IPM malfunction
S Faulty outdoor fan assembly
S Compressor malfunction
S Faulty outdoor PCB
Troubleshooting and Repair:
Check the wiring between
PCB and compressor
Does an error exist ?
Ensure proper connections or
replace the wires and connectors
YES
Check the IPM
NO
Is it in working order ?
Replace the IPM board or
replace the outdoor PCB
NO
Check the outdoor fan and the
outdoor unit ventilation
YES
Is it in working order ?
Refer to the solution
NO
Check the compressor
resistance values.
YES
Are they within
acceptable parameters
?
Replace the compressor
Replace the outdoor PCB
YES
NO