EasyManua.ls Logo

Carrier 40UV - User Manual

Carrier 40UV
72 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 534-094 Printed in U.S.A. Form 40UV,UH-6SI Pg 1 7-05 Replaces: 40UV,UH-3SI
Book 3
Tab 2 a
Installation, Start-Up and Service Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS ............................1
INTRODUCTION ......................................1,2
PREINSTALLATION .....................................1
Unpack and Inspect Units ..............................1
Protect Units From Damage ............................1
Prepare Jobsite for Unit Installation ....................1
Identify and Prepare Units.............................2
PHYSICAL DATA ........................................2
INSTALLATION ......................................2-24
Placing Vertical Units in Position .......................2
Placing Horizontal Units in Position ....................2
Make Piping Connections...............................8
Make Electrical Connections............................8
Actuators (Field-Supplied) ..............................8
Make Duct Connections .............................. 23
Make Final Preparations .............................. 24
PRODUCT INTEGRATED CONTROL ................24-46
Physical Characteristics .............................. 24
Unit Ventilator Comfort Control Module
Installation and Field Wiring ........................ 27
Sensors .............................................. 29
Carrier Comfort Network® Interface .................. 38
Relays ................................................ 39
Actuators ............................................. 39
Direct Expansion (DX) Cooling........................ 41
DX System Design.................................... 41
Electric Heat .......................................... 42
Remote Start ......................................... 42
Fire/Smoke Status Input .............................. 42
Valves ................................................ 43
SET-UP, CONFIGURATION, AND
OPERATION ......................................46-49
START-UP............................................. 50
SERVICE............................................50-66
Preventing Excessive Condensation on Unit.......... 50
Check Drain .......................................... 50
Fan Motor Bearings................................... 50
Fan Shaft Ball Bearing ................................ 50
Clean Fan Wheel...................................... 50
Clean or Replace Air Filters........................... 50
ECM Motor Removal and Reinstallation............... 50
Blower Assembly Section Removal
and Reinstallation .................................. 52
Coil Assembly Removal and Reinstallation ........... 53
Ball Bearing Replacement ............................ 57
Blower Wheel Removal and Reinstallation ............ 62
Sleeve Bearing Replacement ......................... 63
Damper Section Removal and Reinstallation.......... 65
TESTING............................................67-71
Water Valve Tests ..................................... 67
Face and Bypass Damper Tests ...................... 67
Dampers.............................................. 68
Fan Tests ............................................. 68
Filter Maintenance .................................... 68
Remote Start Input.................................... 68
Sensors .............................................. 68
Fire Shutdown Option ................................ 68
Electric Heat and Direct Expansion Cooling .......... 68
Mixed-Air Damper Sensors Final Calibration.......... 69
Testing Completion ................................... 69
Unit Diagnostics and Troubleshooting ................ 69
SAFETY CONSIDERATIONS
Installation and servicing of this unit can be hazardous due
to system pressure, electrical components and equipment
location (such as a ceiling or elevated structure). Untrained
personnel can perform the basic maintenance functions of
replacing filters. Only trained and qualified service personnel
should perform all other operations.
When installing this unit, observe precautions in the litera-
ture, tags and labels attached to the equipment, and any other
safety precautions that may apply.
Follow all safety codes.
Wear safety glasses and work gloves.
Use care in handling and installing this accessory.
Use quenching cloth for all brazing operations.
Have fire extinguisher available for all brazing
operations.
INTRODUCTION
This document contains general installation instructions for
the 40UV,UH unit ventilators and information and trouble-
shooting of the Product Integrated Control (PIC) option.
See submittal drawings for unit configurations, dimensions,
clearances, and pipe connections. Refer to unit wiring label for
all electrical connections; follow NEC (National Electrical
Code) and local codes.
PREINSTALLATION
Unpack and Inspect Units
Remove shipping wraps
from all units. Check the shipment against shipping order. If
shipment is damaged or incomplete, file claim with transporta-
tion company and advise Carrier immediately.
Protect Units From Damage To maintain war-
ranty, protect units against adverse weather, theft, vandalism,
and debris on jobsite. Do not allow foreign material to fall into
drain pan. Prevent dust and debris from being deposited on
motor and fan wheels.
If the equipment is stored for any length of time before in-
stallation, it should remain in its shipping container in a clean,
dry, and climate controlled area.
Prepare Jobsite for Unit Installation To save
time and to reduce the possibility of costly errors, set up a com-
plete sample installation in a typical room at jobsite. Check all
critical dimensions such as pipe, wire, and duct connection
requirements. Refer to job drawings and product dimension
drawings as required. Instruct all trades in their part of the
installation.
Before performing service or maintenance operations, turn
off main power switch to the unit. Electrical shock could
cause personal injury.
40UV,UH050-200
Unit Ventilators
with Product Integrated Control (PIC)

Table of Contents

Other manuals for Carrier 40UV

Questions and Answers

  • B
    Benjamin SullivanAug 15, 2025
    How to troubleshoot a Carrier 40UV unit that does not operate?
    • J
      James WagnerAug 15, 2025
      If the Carrier Fan unit does not operate, there are several potential causes. First, check the local disconnect or circuit breaker to ensure power to the control is on. If the unit is in stand-alone operation, make sure a jumper is installed between T20 on the control module and TB (24 vac). Also, check the LED on the control board. If it's not flashing at a 1-second rate, inspect for loose connections and 24 vac on the POWER connector. Verify the control switch is in the AUTO or CONT position and check for a tripped LLT. Finally, check the status of the Fire Shutdown input to ensure a smoke or fire detector hasn't tripped, and check for shorted wiring.
  • H
    hsheltonAug 25, 2025
    What to do if the mixed air damper on my Carrier 40UV Fan will not operate?
    • A
      Alyssa CastilloAug 26, 2025
      If the Mixed Air Damper on your Carrier Fan will not operate, verify that no forces are present on the MIX1 or MIX2 outputs and remove them if necessary. Check for 24 vac to the actuator; if there's no power, check for open wiring. Confirm that the control is properly configured for the modulating type OA damper. Ensure the temperature sensors are reading correctly and replace any faulty sensors. Verify that the Fan Status reads ON, as dampers require fan operation.
  • J
    Jeremy ChenAug 28, 2025
    Why are the indoor air quality (IAQ) features malfunctioning on my Carrier 40UV Fan?
    • C
      Christopher BrownAug 28, 2025
      If the Indoor Air Quality (IAQ) features on your Carrier Fan are malfunctioning, first enable IAQ control operation. Ensure the set point is correctly adjusted. The control will resume when space/returns temperatures recover if space or return air temperature is too high or low. If the space relative humidity is too high, the control will resume when relative humidity recovers; verify the high humidity limit is configured properly, resetting to 100% if RH control is not used. Normal operation will resume when the MAT sensor is operating properly, if the MAT sensor is shorted, open, or forced; remove the force and repair or replace the MAT sensor.
  • K
    Kevin ReynoldsAug 31, 2025
    What causes the LLT to trip frequently on a Carrier Fan?
    • M
      morenodebraAug 31, 2025
      If the LLT on your Carrier Fan trips frequently, the LLT switch may be malfunctioning and need replacement. Alternatively, the MAT sensor may have failed or be out of calibration; verify the MAT sensor is reading correctly and trim or replace it if necessary.
  • K
    Keith SavageSep 3, 2025
    What causes a Carrier 40UV Fan damper to fail at the minimum position?
    • T
      taylorjerrySep 4, 2025
      If the Damper on your Carrier Fan fails to operate properly at the minimum position, verify sensors are properly calibrated (refer to the test section and repeat the calibration procedure). Also, verify no forces are present on MAT, OAT, or SPT.
  • R
    rossnancySep 7, 2025
    What causes the IAQ level to exceed the set point frequently on a Carrier 40UV?
    • B
      bthompsonSep 7, 2025
      If the IAQ level frequently exceeds the set point (generating alarms) on your Carrier Fan, verify the maximum output value has been correctly set and increase the value in 10% increments if it is too low. If the OAT sensor has failed or is open, normal operation will resume when the OAT sensor is repaired.
  • C
    cody40Sep 12, 2025
    How do I fix a Carrier 40UV Fan temperature sensor that is not reading correctly?
    • A
      Andrew DavisSep 12, 2025
      If the Temperature Sensor on your Carrier Fan is not reading correctly, verify all sensor lead connections are securely fastened. Recheck each sensor reading using a digital thermometer as a reference. Reset the TRIM value to zero before testing each sensor (OAT, MAT, and RAT/SPT). Replace any sensor requiring more than 5 degrees of correction.
  • C
    Christine CohenNov 17, 2025
    Why is my Carrier Fan not heating?
    • R
      Robert HaydenNov 17, 2025
      If your Carrier Fan is not heating, first verify that heating is not being forced disabled by checking the Heating 1, Heating 2, or Heating Enable outputs and removing any forces present. Ensure that there is a supply of hot water, steam, or electricity to the unit, and correct any issues at the source. If you have an electric heater, check if the safety has tripped, and if so, determine the cause (typically insufficient airflow), correct the condition, and reset the safety switch in the heater control box. Verify that the control is configured properly for the type of heat used and that there is 24 vac at the water valve; if not, check for open wiring. Finally, make sure the temperature sensors are reading correctly and that the Fan Status reads ON, as heat will not operate without fan st...
  • M
    michelle02Nov 20, 2025
    Why is my Carrier 40UV not cooling properly?
    • T
      Taylor HunterNov 21, 2025
      If your Carrier Fan is not cooling, begin by verifying that no forces are present in the Cooling 1, Cooling 2, or Heating Enable outputs; remove any forces if found. Check that there is chilled water or electricity available and correct any supply problems. If the condensing unit safety has tripped, determine the cause, correct the condition, and reset the safety switch in the condensing unit control box. Ensure the control is properly configured for the type of cooling used and that there is 24 vac at the water valve; if not, check for open wiring. If the outdoor air temperature is below the DX outdoor air lockout, verify the DX Outdoor Air Lockout setting and the OAT sensor reading. Finally, make sure the temperature sensors are reading correctly and that the Fan Status reads ON, as cool...

Carrier 40UV Specifications

General IconGeneral
BrandCarrier
Model40UV
CategoryFan
LanguageEnglish

Related product manuals