SEE DETAIL A
DETAIL A
Tit
Fig. 20 -- Open Outdoor Unit Control Box Panel
Table 5A -- 38HDV,QRV Electrical Data
38HDV, QRV
UNIT SIZE
0O9
012
V-PH-Hz
208/230-1-60
208/230-1-69
VOLTAGE
RANGE* COMPRESSOR OUTDOOR FAN MOTOR
Min Max RLA LRA FLA NEC Hp kW Out
187 253 3.7 42.3 6.8 0.082 0,06
187 253 4.7 57.9 0.6 0.082 0.06
LEGEND
FLA -- Full Load Amps
LRA -- Locked Rotor Amps
MCA -- Minimum Circuit Amps per NEC Section 439-24
MOCP -- Maximum Overcurrent Protection
NEC -- National Electrical Code
RLA -- Rated Load Amps (Compressor)
MCA MOCP
5.7 15
7.0 15
NOTES:
1. In compliance with NEC requirements for multimotor and combi-
nation load equipment (refer to NEC Articles 439 and 440), the
overcurrent protective device for the unit shall be fuse or
equipped with a breaker.
2. Motor RLA values are established in accordance with UL (Under-
writers Laboratories) Standard 465.
*Permissible limits of the voltage range at which unit will operate
satisfactorily.
o t oo
/,tST_
Table 5B --40QNC,QNQ Fan Coil Electrical Data
40QNC,QNQ
UNIT SIZE
0O9
012
VOLTAGE RANGE*
V-PH-Hz
Min Max
208/230-1-60 187 253
208/230-1-69 187 253
FAN
FLA Motor Power
(Watts)
0.28 48,0
0.28 58.3
POWER
MCA MOCP
0.35 15
0.35 t 5
MIN WIRE
SIZE
14
14
LEGEND NOTES:
FLA -- Full Load Amps 1. In compliance with NEG requirements for multimofor and combi-
MCA -- Minimum Circuit Amps per NEC Section 430-24
MOCP -- Maximum Overcurrent Protection
NEC -- National Electrical Code
RLA -- Rated Load Amps (Compressor) 2.
*Permissible limits of the voltage range at which unit will operate
satisfactorily.
nation load equipment (refer to NEC Articles 430 and 440), the
overcurrent protective device for the unit shall be fuse or
equipped witha breaker.
Motor RLA values are established in accordance with UL (Under-
writers Laboratories) Standard 465.