CHECK VOLTAGE IMBALANCE
LINE-TO-LINE VOLTS: AB_____________ V AC______________ V BC_____________ V
(AB + AC + BC)/3 = AVERAGE VOLTAGE =_____________ V
MAXIMUM DEVIATION FROM AVERAGE VOLTAGE = _______________V
VOLTAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) =______________
IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM!
CALL LOCAL POWER COMPANY FOR ASSISTANCE.
III. START-UP
CHECK INDOOR FAN MOTOR SPEED AND RECORD.
AFTER AT LEAST 10 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS:
COMP A1 COMP B1
OIL PRESSURE ______________ ____________
SUCTION PRESSURE ______________ ____________
SUCTION LINE TEMP ______________ ____________
DISCHARGE PRESSURE ______________ ____________
DISCHARGE LINE TEMP ______________ ____________
ENTERING OUTDOOR UNIT AIR TEMP ______________ ____________
LEAVING OUTDOOR UNIT AIR TEMP ______________ ____________
INDOOR UNIT ENTERING AIR DB TEMP ______________ ____________
INDOOR UNIT ENTERING AIR WB TEMP ______________ ____________
INDOOR UNIT LEAVING AIR DB TEMP ______________ ____________
INDOOR UNIT LEAVING AIR WB TEMP ______________ ____________
OUTDOOR UNIT ENTERING WATER TEMP
(40RFS ONLY) ______________ _____________
OUTDOOR UNIT LEAVING WATER TEMP
(40RFS ONLY) ______________ _____________
INDOOR UNIT ENTERING WATER TEMP
(40RFS ONLY) ______________ _____________
INTDOOR UNIT LEAVING WATER TEMP
(40RFS ONLY) ______________ _____________
COMPRESSOR AMPS (L1/L2/L3) ____/____/____ ____/____/____
CHECK THE COMPRESSOR OIL LEVEL SIGHT GLASSES: ARE THE SIGHT GLASSES SHOWING
OIL LEVEL AT 1/8 to 1/3
FULL? (Y/N)_______________
NOTES:
________________________________________________________________________________________________
________________________________________________________________________________________________
________________________________________________________________________________________________
________________________________________________________________________________________________
________________________________________________________________________________________________
________________________________________________________________________________________________