12
Table 2 — Electric Heater Data for Units with PSC Motor
LEGEND
*Cooling coil must be left-hand coil connections only.
NOTES:
1. LAT (leaving air temperature) is at maximum fan speed with
entering air temperature at 70°F.
2. Face and bypass units are available only with 3 elements.
3. Electric heat is available in the reheat only position.
4. The PSC motor is not available on unit size 200.
UNIT HP
NOMINAL
V/Ph/Hz
NUMBER OF
ELEMENTS
FLA LAT (F) MCA MOCP
TOTAL
CAPACITY (kW)
40UV050
(at 500 cfm)
1
/
5
208/1/60
3 17.2 90 21.5 25 3.2
4 22.2 97 27.8 30 4.2
5 27.3 104 34.1 35 5.3
6 32.3 110 40.4 45 6.3
240/1/60
3 19.5 97 24.4 25 4.2
4 25.3 106 31.7 35 5.6
5 31.2 115 39.0 40 7.0
6 37.0 124 46.3 50 8.4
277/1/60
3 16.8 97 21.0 25 4.2
4 21.8 106 27.3 30 5.6
5 26.9 115 33.6 35 7.0
6 31.9 124 39.9 40 8.4
208/3/60
3 10.8 90 13.5 15 3.2
4 15.8 97 19.8 20 4.2
5 19.5 104 24.4 25 5.3
6 19.5 110 24.4 25 6.3
240/3/60
3 12.1 97 15.1 20 4.2
4 17.9 106 22.4 25 5.6
5 22.2 115 27.8 30 7.0
6 22.2 124 27.8 30 8.4
460/3/60
3 6.0 97 7.5 15 4.2
4 8.9 106 11.1 15 5.6
5 11.0 115 13.8 15 7.0
6 11.0 124 13.8 15 8.4
40UV,UH075
(at 750 cfm)
1
/
5
208/1/60
3 23.7 89 29.6 30 4.5
4 30.9 96 38.6 40 6.0
5 38.1 102 47.6 50 7.5
6 45.3 108 56.7 60 9.0
240/1/60
3 27.0 96 33.8 35 6.0
4 35.3 104 44.2 45 8.0
5 43.7 113 54.6 60 10.0
6 52.0 121 65.0 70 12.0
277/1/60
3 23.3 96 29.1 30 6.0
4 30.5 104 38.1 40 8.0
5 37.7 113 47.1 50 10.0
6 44.9 121 56.2 60 12.0
208/3/60
3 14.5 89 18.2 20 4.5
4 21.7 96 27.2 30 6.0
5 27.0 102 33.8 35 7.5
6 27.0 108 33.8 35 9.0
240/3/60
3 16.5 96 20.6 25 6.0
4 24.8 104 31.0 35 8.0
5 30.9 113 38.6 40 10.0
6 30.9 121 38.6 40 12.0
460/3/60
3 8.2 96 10.2 15 6.0
4 12.3 104 15.4 20 8.0
5 15.4 113 19.2 20 10.0
6 15.4 121 19.2 20 12.0
FLA — Full Load Amps
LAT — Leaving-Air Temperature at 70°F Entering-Air
Temperature
MCA — Unit Minimum Circuit Ampacity
MOCP — Maximum Overcurrent Protection (Maximum Fuse Size
or Circuit Breaker Amps)
PSC — Permanent Split Capacitor