13
Table 2 — Electric Heater Data for Units with PSC Motor (cont)
LEGEND
*Cooling coil must be left-hand coil connections only.
NOTES:
1. LAT (leaving air temperature) is at maximum fan speed with
entering air temperature at 70°F.
2. Face and bypass units are available only with 3 elements.
3. Electric heat is available in the reheat only position.
4. The PSC motor is not available on unit size 200.
UNIT HP
NOMINAL
V/Ph/Hz
NUMBER OF
ELEMENTS
FLA LAT (F) MCA MOCP
TOTAL
CAPACITY (kW)
40UV,UH100
(at 1000 cfm)
1
/
5
208/1/60
3 30.9 89 38.6 40 6.0
4 40.5 95 50.7 60 8.0
5 50.2 102 62.7 70 10.0
6 59.8 108 74.7 80 11.9
240/1/60
3 35.3 96 44.2 45 8.0
4 46.5 104 58.1 60 10.7
5 57.6 112 72.0 80 13.3
6 68.7 121 85.8 90 16.0
277/1/60
3 30.5 96 38.1 40 8.0
4 40.1 104 50.1 60 10.7
5 49.7 112 62.2 70 13.3
6 59.4 121 74.2 80 16.0
208/3/60
3 18.7 89 23.4 25 6.0
4 28.3 95 35.4 40 8.0
5 35.4 102 44.3 45 10.0
6 35.4 108 44.3 45 11.9
240/3/60
3 21.3 96 26.6 30 8.0
4 32.4 104 40.5 45 10.7
5 40.5 112 50.7 60 13.3
6 40.5 121 50.7 60 16.0
460/3/60
3 10.6 96 13.2 15 8.0
4 16.1 104 20.1 25 10.7
5 20.2 112 25.2 30 13.3
6 20.2 121 25.2 30 16.0
40UV,UH125
(at 1250 cfm)
1
/
5
208/1/60
3 38.1 89 47.6 50 7.5
4 50.1 96 62.7 70 10.0
5 62.2 102 77.7 80 12.5
6* 74.2 108 92.8 100 15.0
240/1/60
3 43.7 96 54.6 60 10.0
4 57.6 104 71.9 80 13.3
5 71.4 113 89.3 90 16.7
6* 85.3 121 106.7 110 20.0
277/1/60
3 37.7 96 47.1 50 10.0
4 49.7 104 62.2 70 13.3
5 61.8 113 77.2 80 16.7
6* 73.8 121 92.2 100 20.0
208/3/60
3 22.9 89 28.6 30 7.5
4 34.9 96 43.6 45 10.0
5 43.7 102 54.7 60 12.5
6* 43.7 108 54.7 60 15.0
240/3/60
3 26.1 96 32.6 35 10.0
4 40.0 104 50.0 50 13.3
5 50.2 113 62.7 70 16.7
6* 50.2 121 62.7 70 20.0
460/3/60
3 13.0 96 16.2 20 10.0
4 19.9 104 24.9 25 13.3
5 25.0 113 31.3 35 16.7
6* 25.0 121 31.3 35 20.0
FLA — Full Load Amps
LAT — Leaving-Air Temperature at 70°F Entering-Air
Temperature
MCA — Unit Minimum Circuit Ampacity
MOCP — Maximum Overcurrent Protection (Maximum Fuse Size
or Circuit Breaker Amps)
PSC — Permanent Split Capacitor