Table 2 — Electric Heater Data for Units with PSC Motor (cont)
LEGEND
*Cooling coil must be left-hand coil connections only.
NOTES:
1. LAT (leaving air temperature) is at maximum fan speed with
entering air temperature at 70°F.
2. Face and bypass units are available only with 3 elements.
3. Electric heat is available in the reheat only position.
4. The PSC motor is not available on unit size 200.
UNIT HP
NOMINAL
V/Ph/Hz
NUMBER OF
ELEMENTS
FLA LAT (F) MCA MOCP
TOTAL
CAPACITY (kW)
40UV,UH150
(at 1500 cfm)
1
/
5
208/1/60
3 45.3 89 56.7 60 9.0
4 59.8 96 74.7 80 12.0
5 74.2 102 92.8 100 15.0
6* 88.7 108 110.8 125 18.0
240/1/60
3 52.0 96 65.0 70 12.0
4 68.7 104 85.8 90 16.0
5 85.3 113 106.7 110 20.0
6—
277/1/60
3 44.9 96 56.2 60 12.0
4 59.4 104 74.2 80 16.0
5 73.8 113 92.3 100 20.0
6—
208/3/60
3 27.0 89 33.8 35 9.0
4 41.5 96 51.9 60 12.0
5 52.1 102 65.1 70 15.0
6* 52.1 108 65.1 70 18.0
240/3/60
3 30.9 96 38.6 40 12.0
4 47.6 104 59.5 60 16.0
5 59.8 113 74.8 80 20.0
6* 59.8 121 74.8 80 24.0
460/3/60
3 15.4 96 19.2 20 12.0
4 23.7 104 29.6 30 16.0
5 29.8 113 37.3 40 20.0
6* 29.8 121 37.3 40 24.0
FLA Full Load Amps
LAT Leaving-Air Temperature at 70°F Entering-Air
Temperature
MCA Unit Minimum Circuit Ampacity
MOCP Maximum Overcurrent Protection (Maximum Fuse Size
or Circuit Breaker Amps)
PSC Permanent Split Capacitor