Table 3 — Electric Heater Data for Units with ECM Motor (cont)
LEGEND
*Cooling coil must be left-hand coil connections only
NOTES:
1. LAT (leaving air temperature) is at maximum fan speed with
entering air temperature at 70°F.
2. Face and bypass units are available only with 3 elements.
3. Electric heat is available in the reheat only position.
UNIT HP
NOMINAL
V/Ph/Hz
NUMBER OF
ELEMENTS
FLA LAT (F) MCA MOCP
TOTAL
CAPACITY (kW)
40UV,UH100
(at 1000 cfm)
1
/
3
208/1/60
3 31.5 89 39.4 40 6.0
4 41.1 95 51.4 60 8.0
5 50.8 102 63.4 70 10.0
6 60.4 108 75.5 80 11.9
240/1/60
3 35.9 96 44.9 45 8.0
4 47.1 104 58.8 60 10.7
5 58.2 112 72.7 80 13.3
6 69.3 121 86.6 90 16.0
277/1/60
3 31.2 96 39.0 40 8.0
4 40.8 104 51.0 60 10.7
5 50.4 112 63.1 70 13.3
6 60.1 121 75.1 80 16.0
208/3/60
3 19.3 89 24.1 25 6.0
4 28.9 95 36.2 40 8.0
5 36.0 102 45.0 50 10.0
6 36.0 108 45.0 50 11.9
240/3/60
3 21.9 96 27.3 30 8.0
4 33.0 104 41.2 45 10.7
5 41.1 112 51.4 60 13.3
6 41.1 121 51.4 60 16.0
460/3/60
3 10.6 96 13.3 15 8.0
4 16.2 104 20.2 25 10.7
5 20.3 112 25.3 30 13.3
6 20.3 121 25.3 30 16.0
40UV,UH125
(at 1250 cfm)
1
/
2
208/1/60
3 39.4 89 49.3 50 7.5
4 51.5 96 64.3 70 10.0
5 63.5 102 79.4 80 12.5
6* 75.5 108 94.4 100 15.0
240/1/60
3 45.0 96 56.2 60 10.0
4 58.9 104 73.6 80 13.3
5 72.7 113 90.9 100 16.7
6* 86.6 121 108.3 110 20.0
277/1/60
3 39.0 96 48.7 50 10.0
4 51.0 104 63.8 70 13.3
5 63.1 113 78.8 80 16.7
6* 75.1 121 93.9 100 20.0
208/3/60
3 24.2 89 30.2 35 7.5
4 36.2 96 45.3 50 10.0
5 45.0 102 56.3 60 12.5
6* 45.0 108 56.3 60 15.0
240/3/60
3 27.4 96 34.2 35 10.0
4 41.3 104 51.6 60 13.3
5 51.5 113 64.3 70 16.7
6* 51.5 121 64.3 70 20.0
460/3/60
3 13.2 96 16.5 20 10.0
4 20.2 104 25.2 30 13.3
5 25.3 113 31.6 35 16.7
6* 25.3 121 31.6 35 20.0
ECM Electronically Commutated Motor
FLA Full Load Amps
LAT Leaving-Air Temperature at 70°F Entering-Air
Temperature
MCA Unit Minimum Circuit Ampacity
MOCP Maximum Overcurrent Protection (Maximum Fuse Size
or Circuit Breaker Amps)