17
Table 3 — Electric Heater Data for Units with ECM Motor (cont)
LEGEND
*Cooling coil must be left-hand coil connections only.
NOTES:
1. LAT (leaving air temperature) is at maximum fan speed with
entering air temperature at 70°F.
2. Face and bypass units are available only with 3 elements.
3. Electric heat is available in the reheat only position.
UNIT HP
NOMINAL
V/Ph/Hz
NUMBER OF
ELEMENTS
FLA LAT (F) MCA MOCP
TOTAL
CAPACITY (kW)
40UV,UH150
(at 1500 cfm)
1
/
2
208/1/60
3 46.7 89 58.3 60 9.0
4 61.1 96 76.4 80 12.0
5 75.6 102 94.4 100 15.0
6* 90.0 108 112.5 125 18.0
240/1/60
3 53.3 96 66.6 70 12.0
4 70.0 104 87.5 90 16.0
5 86.6 113 108.3 110 20.0
6—————
277/1/60
3 46.2 96 57.8 60 12.0
4 60.7 104 75.8 80 16.0
5 75.1 113 93.9 100 20.0
6—————
208/3/60
3 28.3 89 35.4 40 9.0
4 42.8 96 53.5 60 12.0
5 53.4 102 66.7 70 15.0
6* 53.4 108 66.7 70 18.0
240/3/60
3 32.2 96 40.3 45 12.0
4 48.9 104 61.1 70 16.0
5 61.1 113 76.4 80 20.0
6* 61.1 121 76.4 80 24.0
460/3/60
3 15.6 96 19.5 20 12.0
4 24.0 104 30.0 30 16.0
5 30.1 113 37.6 40 20.0
6* 30.1 121 37.6 40 24.0
40UH200
(at 2000 cfm)
3
/
4
208/1/60
3 50.1 84 62.7 70 9.0
4 64.6 89 80.7 90 12.0
5 79.0 94 98.8 100 15.0
6* 93.5 99 116.8 125 18.0
240/1/60
3 56.8 89 71.0 80 12.0
4 73.5 96 91.8 100 16.0
5 90.1 102 112.7 125 20.0
6—————
277/1/60
3 48.8 89 61.0 70 12.0
4 63.3 96 79.1 80 16.0
5 77.7 102 97.1 100 20.0
6—————
208/3/60
3 31.8 84 39.8 40 9.0
4 46.3 89 57.9 60 12.0
5 56.9 94 71.1 80 15.0
6* 56.9 99 71.1 80 18.0
240/3/60
3 35.7 89 44.6 45 12.0
4 52.4 96 65.5 70 16.0
5 64.6 102 80.8 90 20.0
6* 64.6 108 80.8 90 24.0
460/3/60
3 16.9 89 21.1 25 12.0
4 25.2 96 31.5 35 16.0
5 31.3 102 39.1 40 20.0
6* 31.3 108 39.1 40 24.0
ECM — Electronically Commutated Motor
FLA — Full Load Amps
LAT — Leaving-Air Temperature at 70°F Entering-Air
Temperature
MCA — Unit Minimum Circuit Ampacity
MOCP — Maximum Overcurrent Protection (Maximum Fuse Size
or Circuit Breaker Amps)