18
Table 4 — Motor Data
PSC Motor Data
ECM Motor Data
LEGEND
*Available in vertical configuration only.
†Available in horizontal configuration only.
NOTE: The PSC motor is not available on unit size 200.
UNIT 40UV,UH SIZE MOTOR Hp VOLTAGE FLA MCA MOP (Amps)
MAX FUSE SIZE
(Amps)
050*
1
/
5
115 3.7 4.6 8.3 15
208/230 2.0 2.5 4.5 15
265 1.6 2.0 3.6 15
075
1
/
5
115 3.7 4.6 8.3 15
208/230 2.0 2.5 4.5 15
265 1.6 2.0 3.6 15
100
1
/
5
115 3.7 4.6 8.3 15
208/230 2.0 2.5 4.5 15
265 1.6 2.0 3.6 15
125
1
/
5
115 3.7 4.6 8.3 15
208/230 2.0 2.5 4.5 15
265 1.6 2.0 3.6 15
150
1
/
5
115 3.7 4.6 8.3 15
208/230 2.0 2.5 4.5 15
265 1.6 2.0 3.6 15
UNIT 40UV,UH SIZE MOTOR Hp VOLTAGE FLA MCA MOP (Amps)
MAX FUSE SIZE
(Amps)
050*
1
/
3
115 1.4 1.8 3.1 15
208/230 1.3 1.6 2.9 15
265 1.1 1.4 2.6 15
075
1
/
3
115 3.7 4.6 8.3 15
208/230 2.3 2.9 5.1 15
265 2.0 2.5 4.5 15
100
1
/
3
115 4.0 5.0 9.1 15
208/230 2.6 3.2 5.8 15
265 2.3 2.9 5.1 15
125
1
/
2
115 4.7 5.9 10.6 15
208/230 3.3 4.1 7.4 15
265 2.9 3.6 6.6 15
150
1
/
2
115 4.7 5.9 10.6 15
208/230 3.3 4.1 7.4 15
265 2.9 3.6 6.6 15
200†
3
/
4
115 9.6 12.0 21.6 20
208/230 6.8 8.5 15.3 15
265 5.5 6.9 12.4 15
ECM Electronically Commutated Motor
FLA Full Load Amps
MCA Minimum Circuit Amps
MOP Maximum Overload Protection
PSC Permanent Split Capacitor