EasyManua.ls Logo

Carrier 40UV075 - Page 19

Carrier 40UV075
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
19
Fig. 13 — 115-v PSC Motor without Controls
SW2
See Tap
BLK
RED
WHT
FAN
MOTOR
SW1
WHT/110
BLK/101
WHT/110
BLK/102
FU1
USE COPPER SUPPLY WIRES.
115 V
L1
N
GND
RED BLK
WHT
3
2
1
1
2
3
LLT
WHT
WHT
BLK/104
BLK/100
BLK/103
BLK/104
SEE NOTE 2
DISC1
GRN
TRAN3
SEE NOTE 3
MAX
LOW
HIGH
LLR
3
1
2
FIELD CONNECTED TO
REMOTE CONDENSER.
LLR INSTALLED ONLY ON
UNITS WITH DX COILS.
Select Drawing
NOTES:
1. Make electrical installation in accordance with job
diagram, and in compliance with national and local
electrical codes.
2. Low limit thermostat (LLT) is installed on all units with
water coils.
3. Unused transformer leads are separately insulated.
LEGEND
DISC Disconnect Switch
DX Direct Expansion
FU Fuse
GND Ground
LLR DX Low Limit Switch
LLT Water Coil Low Limit Thermostat
PSC Permanent Split Capacitor
SW Switch
TRAN Transformer
Splice Terminal Connection
Component Tie Point
Optional Wiring
Factory Wiring
Chassis Ground