11
42BHC 4-ROW COOLING CAPACITY (by Gpm)
LEGEND NOTE: All capacities are given in thousands of Btuh (MBtuh).
42BHC 6-ROW COOLING CAPACITY (by Gpm)
LEGEND NOTE: All capacities are given in thousands of Btuh (MBtuh).
UNIT
SIZE
42BHC
GPM
75 F DB/ 63 F WB 80 F DB/67 F WB 85 F DB/71 F WB
40 F EWT 45 F EWT 50 F EWT 40 F EWT 45 F EWT 50 F EWT 40 F EWT 45 F EWT 50 F EWT
TTC
b
SC
b
TTC
b
SC
b
TTC
b
SC
b
TTC
b
SC
b
TTC
b
SC
b
TTC
b
SC
b
TTC
b
SC
b
TTC
b
SC
b
TTC
b
SC
b
08
2 15.9 15.9 14.3 13.8 13.8 12.8 11.0 11.0 11.0 18.4 18.4 15.7 16.3 16.3 14.5 14.2 14.2 13.0 21.1 21.1 17.0 18.9 18.9 16.0 16.8 16.8 14.8
3 12.7 19.1 16.2 10.9 16.3 14.7 9.2 13.8 12.9 15.0 22.5 17.7 13.0 19.5 16.4 11.2 16.7 15.0 17.4 26.1 19.1 15.3 23.0 17.9 13.3 20.0 16.6
4 10.7 21.5 17.4 9.0 18.0 15.7 7.5 14.9 13.9 12.8 25.6 19.0 11.0 21.9 17.5 9.2 18.4 16.0 15.0 30.0 20.6 13.1 26.2 19.2 11.2 22.4 17.7
5 9.3 23.3 18.2 7.7 19.4 16.4 6.3 15.7 14.6 11.2 28.0 20.1 9.5 23.8 18.3 7.9 19.7 16.6 13.2 33.1 21.8 11.5 28.7 20.1 9.7 24.3 18.5
6 8.3 24.8 18.9 6.8 20.4 16.9 5.4 16.3 15.0 10.0 30.0 20.9 8.4 25.3 19.0 6.9 20.7 17.1 11.8 35.5 22.8 10.2 30.7 20.9 8.6 25.8 19.1
12
3 17.3 26.0 22.5 15.0 22.6 20.4 11.8 17.7 17.7 20.2 30.2 24.7 17.8 26.7 22.9 15.5 23.2 20.8 23.2 34.7 26.6 20.7 31.0 25.0 18.3 27.4 23.2
4 14.7 29.5 24.5 12.6 25.2 22.3 10.6 21.2 19.6 17.3 34.7 26.8 15.1 30.1 24.8 12.9 25.8 22.6 20.2 40.3 29.0 17.7 35.5 27.1 15.4 30.8 25.1
5 12.9 32.2 25.9 10.9 27.2 23.5 9.0 22.6 20.8 15.3 38.3 28.4 13.1 32.9 26.2 11.1 27.7 23.8 17.9 44.8 30.8 15.6 39.1 28.6 13.4 33.5 26.4
6 11.5 34.4 27.0 9.6 28.7 24.4 7.8 23.5 21.6 13.7 41.2 29.7 11.7 35.1 27.1 9.7 29.1 24.6 16.2 48.5 32.2 14.0 42.1 29.7 11.9 35.6 27.3
16
5 14.9 37.3 31.7 12.9 32.3 28.8 10.0 25.0 25.0 17.5 43.7 34.6 15.3 38.3 32.2 13.3 33.2 29.3 20.2 50.6 37.4 17.9 44.9 35.1 15.7 39.4 32.7
7 12.3 42.9 34.6 10.4 36.3 31.4 8.6 30.2 27.7 14.6 51.0 37.9 12.5 43.8 34.9 10.6 37.0 31.8 17.1 59.7 41.0 14.9 52.2 38.1 12.8 44.8 35.3
9 10.4 47.0 36.5 8.7 39.1 32.9 7.1 31.9 29.2 12.5 56.4 40.2 10.7 48.0 36.7 8.8 39.7 33.3 14.8 66.4 43.7 12.8 57.7 40.3 10.8 48.8 36.9
11 9.1 50.1 37.9 7.5 41.2 34.0 6.0 33.0 30.0 11.0 60.4 42.0 9.3 51.0 38.0 7.6 41.7 34.2 13.0 71.5 45.7 11.2 61.6 41.8 9.4 51.8 38.1
20
5 17.6 43.9 37.8 15.3 38.2 34.2 11.8 29.5 29.5 20.4 51.1 41.4 18.1 45.1 38.4 15.7 39.4 34.8 23.5 58.7 44.6 21.0 52.5 42.0 18.6 46.5 39.0
7 14.5 50.7 41.6 12.4 43.2 37.8 10.4 36.3 33.3 17.1 59.8 45.5 14.8 51.8 42.0 12.7 44.3 38.3 19.9 69.6 49.2 17.5 61.1 45.9 15.1 52.9 42.5
9 12.4 55.7 44.1 10.4 46.7 39.9 8.6 38.6 35.3 14.8 66.4 48.4 12.6 56.8 44.4 10.6 47.5 40.3 17.3 77.9 52.5 15.1 67.8 48.6 12.8 57.6 44.7
11 10.8 59.6 45.9 9.0 49.3 41.3 7.3 40.0 36.5 13.0 71.6 50.6 11.0 60.5 46.0 9.1 50.0 41.6 15.3 84.3 55.0 13.2 72.7 50.5 11.2 61.4 46.2
30
7 17.7 61.8 54.4 15.4 54.0 49.0 11.9 41.8 41.8 20.5 71.7 59.9 18.2 63.8 55.4 16.0 55.8 49.9 23.5 82.1 64.7 21.1 73.9 60.9 18.8 65.9 56.4
9 15.5 69.6 59.2 13.4 60.3 53.8 10.3 46.5 46.5 18.1 81.5 64.9 15.9 71.6 60.2 13.8 62.1 54.7 20.9 94.1 70.0 18.6 83.7 65.7 16.4 73.6 61.1
11 13.8 76.0 62.7 11.8 65.0 57.0 9.9 54.6 50.1 16.3 89.7 68.6 14.1 77.8 63.4 12.1 66.6 57.8 19.0 104.4 74.1 16.7 91.8 69.2 14.5 79.6 64.2
14 11.9 83.4 66.3 10.0 70.2 60.1 8.3 58.1 53.1 14.2 99.4 72.8 12.2 85.2 66.9 10.2 71.6 60.8 16.7 116.6 78.9 14.5 101.7 73.2 12.4 87.0 67.5
17 10.5 89.3 69.1 8.7 74.2 62.2 7.1 60.4 55.0 12.6 107.1 76.1 10.7 91.2 69.5 8.9 75.3 62.8 14.9 126.3 82.7 12.9 109.7 76.3 10.9 92.5 69.8
40
11 17.5 96.3 80.5 15.2 83.3 73.0 12.9 70.8 63.9 20.5 112.5 88.0 18.0 98.7 81.4 15.6 85.7 74.0 23.6 129.7 94.8 20.9 115.2 88.8 18.4 101.3 82.4
14 15.1 106.0 85.7 12.9 90.4 77.8 10.9 76.0 68.6 17.9 125.2 93.9 15.5 108.3 86.5 13.2 92.6 78.8 20.8 145.6 101.4 18.3 127.9 94.4 15.8 110.7 87.4
17 13.4 113.9 89.6 11.3 95.8 81.0 9.3 79.3 71.6 15.9 135.5 98.4 13.7 116.2 90.2 11.5 97.3 81.8 18.7 158.7 106.6 16.3 138.4 98.6 13.8 117.7 90.6
21 11.6 122.3 93.6 9.7 101.8 84.3 7.9 82.5 74.3 13.9 146.4 103.1 11.9 124.8 94.0 9.8 102.8 84.7 16.4 172.1 111.9 14.3 149.7 103.1 12.0 126.1 94.1
25 10.3 129.1 96.7 8.5 105.8 86.2 6.8 84.4 75.9 12.4 155.3 106.9 10.5 130.7 96.5 8.5 106.6 86.6 14.7 183.3 116.3 12.6 157.7 106.2 10.6 132.0 96.5
DB
Dry Bulb Temperature
EWT
Entering Water Temperature
MBtuh
Thousands of Btuh
SC
b
Base Sensible Capacity at Nominal Cfm
TC
b
Base Total Capacity at Nominal Cfm
WB
Wet Bulb Temperature
T—
Change in Water Temperature (F)
UNIT
SIZE
42BHC
GPM
75 F DB/ 63 F WB 80 F DB/67 F WB 85 F DB/71 F WB
40 F EWT 45 F EWT 50 F EWT 40 F EWT 45 F EWT 50 F EWT 40 F EWT 45 F EWT 50 F EWT
TTC
b
SC
b
TTC
b
SC
b
TTC
b
SC
b
TTC
b
SC
b
TTC
b
SC
b
TTC
b
SC
b
TTC
b
SC
b
TTC
b
SC
b
TTC
b
SC
b
08
3 16.0 24.1 19.1 13.6 20.5 17.4 10.4 15.6 15.6 19.0 28.5 20.9 16.4 24.6 19.3 14.0 21.0 17.8 22.2 33.3 22.6 19.5 29.2 21.1 16.8 25.2 19.5
4 13.5 27.0 20.5 11.3 22.6 18.5 9.3 18.7 16.6 16.2 32.3 22.6 13.8 27.6 20.6 11.5 23.1 18.7 19.1 38.2 24.6 16.5 33.1 22.6 14.1 28.2 20.7
5 11.7 29.2 21.5 9.7 24.2 19.3 7.8 19.5 17.1 14.1 35.3 23.8 11.9 29.8 21.5 9.8 24.6 19.4 16.7 41.8 26.0 14.5 36.2 23.8 12.2 30.5 21.6
6 10.3 30.9 22.3 8.5 25.4 19.8 6.7 20.1 17.5 12.5 37.5 24.8 10.5 31.6 22.3 8.6 25.8 19.9 14.9 44.6 27.2 12.9 38.6 24.7 10.7 32.2 22.3
12
6 14.3 42.8 31.7 11.8 35.5 28.5 9.7 29.0 25.4 17.2 51.5 35.1 14.5 43.6 31.8 12.0 36.1 28.7 —— ——— ———
8 11.7 46.8 33.6 9.5 38.2 29.7 7.6 30.3 26.2 14.2 56.7 37.4 11.9 47.5 33.5 9.6 38.6 29.8 20.3 60.9 38.2 17.6 52.7 35.0 14.8 44.3 31.8
10 9.9 49.3 34.8 8.0 39.9 30.5 6.2 31.2 26.7 12.0 59.8 38.8 10.0 50.1 34.6 8.1 40.3 30.5 14.2 71.1 42.5 12.2 61.2 38.4 10.2 50.9 34.4
16
7 15.4 53.8 40.8 13.0 45.3 37.0 10.8 37.9 33.2 18.4 64.3 45.0 15.7 55.0 41.0 13.3 46.4 37.4 21.6 75.7 48.8 18.8 65.7 44.9 16.1 56.3 41.3
9 13.0 58.7 43.2 10.8 48.7 38.6 8.8 39.7 34.4 15.7 70.8 47.8 13.3 60.0 43.2 11.0 49.5 38.8 18.6 83.8 52.1 16.1 72.6 47.6 13.6 61.0 43.2
11 11.4 62.5 44.9 9.3 51.1 39.8 7.4 40.8 35.1 13.7 75.6 49.9 11.6 63.5 44.7 9.4 51.9 39.9 16.3 89.6 54.5 14.0 77.2 49.4 11.7 64.6 44.6
13 10.1 65.3 46.2 8.2 53.1 40.7 6.4 41.7 35.6 12.2 79.2 51.5 10.2 66.5 45.9 8.2 53.6 40.6 14.5 94.0 56.4 12.5 81.0 50.9 10.4 67.4 45.7
20
7 18.1 63.3 49.1 15.4 53.9 44.7 11.4 39.8 39.8 18.0 63.0 63.0 15.9 55.5 55.5 13.7 47.9 47.9 25.2 88.0 58.3 21.9 76.8 53.9 18.9 66.2 49.9
9 15.4 69.5 52.1 12.9 58.1 46.9 10.7 48.3 42.1 14.9 67.0 67.0 13.1 59.0 59.0 11.3 50.8 50.8 21.9 98.4 62.4 18.9 85.1 57.3 16.0 71.9 52.2
11 13.5 74.3 54.3 11.1 61.2 48.4 9.0 49.7 43.1 12.7 69.6 69.6 11.1 61.1 61.1 9.6 52.6 52.6 19.2 105.8 65.5 16.6 91.5 59.8 13.9 76.7 54.0
13 12.0 78.1 56.1 9.8 63.7 49.5 7.8 50.8 43.8 11.0 71.4 71.4 9.6 62.6 62.6 8.3 53.8 53.8 17.2 111.7 67.9 14.8 96.1 61.6 12.3 80.1 55.4
15 10.8 80.7 57.3 8.7 65.6 50.4 6.9 51.6 44.2 9.7 72.6 72.6 8.5 63.6 63.6 7.3 54.6 54.6 15.5 115.9 69.7 13.3 99.8 63.0 11.1 83.1 56.6
30
11 17.4 95.7 74.2 14.8 81.6 67.6 12.5 69.1 60.5 20.6 113.5 81.3 17.8 98.1 74.8 15.2 83.8 68.6 24.2 133.0 88.1 21.1 116.2 81.6 18.3 100.4 75.5
14 15.0 104.7 78.5 12.5 87.8 70.8 10.4 73.1 63.6 17.9 125.6 86.6 15.3 107.1 78.7 12.8 89.8 71.6 21.1 148.0 94.1 18.4 128.5 86.4 15.6 109.3 79.1
17 13.2 111.8 81.8 10.9 92.7 73.1 8.9 75.4 65.1 15.9 134.9 90.6 13.4 114.1 81.7 11.1 94.1 73.5 18.8 159.5 98.7 16.3 138.2 90.2 13.6 115.9 81.6
21 11.3 119.0 85.2 9.3 97.2 75.2 7.4 77.5 66.3 13.7 144.0 94.5 11.6 121.5 84.9 9.4 98.7 75.5 16.2 170.5 103.3 14.1 147.6 93.9 11.7 123.1 84.4
40
17 16.7 141.6 105.5 14.0 118.9 95.1 11.7 99.3 85.5 20.0 169.6 116.4 17.0 144.4 105.6 14.2 121.0 95.8 23.5 199.6 126.3 20.3 172.6 115.7 17.2 146.3 105.6
21 14.5 151.8 110.4 12.0 126.0 98.5 9.8 102.5 87.6 17.4 182.5 121.9 14.7 154.6 109.9 12.2 127.6 98.8 20.6 216.6 133.3 17.8 186.7 121.2 14.9 156.7 109.6
25 12.8 159.8 114.1 10.4 130.6 100.7 8.3 104.3 88.8 15.4 192.9 126.5 13.0 162.2 113.3 10.6 132.2 100.8 18.2 228.1 138.1 15.7 196.6 125.1 13.1 164.1 112.6
DB
Dry Bulb Temperature
EWT
Entering Water Temperature
MBtuh
Thousands of Btuh
SC
b
Base Sensible Capacity at Nominal Cfm
TC
b
Base Total Capacity at Nominal Cfm
WB
Wet Bulb Temperature
T—
Change in Water Temperature (F)