42BHC ELECTRIC HEATER DATA AVAILABILITY 42BHC ELECTRIC HEATER DATA
LEGEND
NOTES:
1. Stages available:
Single phase:1-4 kW, 1 stage only
5-12 kW, 1 stage or 2 stage
Three phase:1-12 kW, 1 stage only
15-20 kW, 1 or 2 stage
25-40 kW, 1, 2 or 3 stage
2. Electric Heating Capacities (Btuh) = Heater kW x 3413
3. Electric Heater Amperage for Single-phase Power = (Heater kW x 1000)/Applied Voltage Electric Heater Amperage for Three-phase Power = (Heater kW x 1000)/(Applied Voltage x 1.73).
MOTOR PERFORMANCE DATA (AMPS)
NOTES:
1. Motor Full Load Amps refer to National Electric Code (NEC) Amps;
actual motor nameplate amps may vary.
2. NEC data extrapolated for 277 v.
3. Motors are open drip proof, ball bearing, single speed, 1750 rpm
rated at continuous duty, 40° C (104° F) ambient with reversible
rotation.
Controls
Standard control features
4 in. x 4 in. junction box
Note that the motor leads are wired to the 4 in. x 4 in.
junction box which is mounted on the external panel.
Motor control options
Interlocking disconnect switch*
24-v class 2 transformer (40 va)†
8-pole control terminal strip
Motor power fusing*
Motor control contactor**
Motor and electric heat control options
NOTE: Electric heat option requires same voltage as motor
and must include the control option. These control features
are standard with electric heat options and control option.
Interlocking disconnect switch*
Heater power fusing*
24-v class 2 transformer (40 va)†
8-pole control terminal strip
Auto reset temperature limit switch
Manual reset backup temperature limit switch
Airflow safety switch
80/20 heater element wire
Motor power fusing*
Motor control contactor**
Agency listed for 0-in. clearance
Electric heat options:
Single-phase, single-stage or 2-stage heat
Three-phase, single-stage, 2- or 3-stage heat
*Complies with NECs fused disconnect requirement.
No control fusing necessary.
**Complies with NECs requirement for a motor starter with internal
heating elements when used with the factorys standard motors with
integral thermal overload protection.
kW
42BHC UNIT SIZE
08 12 16 20 30 40
1
—————
2
●●
————
3
●●●
———
4
●●●●
——
5
●●●●
——
6
●●●●●●
8
●●●●●●
10
●●●●●
12
●●●●●
15
——
●●●●
16
——
●●●●
20
———
●●●
25
————
●●
30
————
●●
35
—————
40
—————
kW
FULL LOAD AMPS
Single-Phase Three-Phase
120 V 208 V 240 V 277 V 208 V 240 V 480 V
1
8.3 4.8 4.2 3.6 2.8 2.4 1.2
2
16.79.68.37.25.64.82.4
3
25.0 14.4 12.5 10.8 8.3 7.2 3.6
4
33.3 19.2 16.7 14.4 11.1 9.6 4.8
5
41.724.020.818.113.912.0 6.0
6
28.825.021.716.714.4 7.2
8
38.533.328.922.219.2 9.6
10
47.641.335.727.523.811.9
12
———43.3 33.3 28.9 14.4
15
————41.6 36.1 18.0
16
————44.4 38.5 19.2
20
—————47.9 23.9
25
——————30.1
30
——————36.1
35
——————42.1
40
——————48.0
Standard Offering
VOLTAGE
V-PH- Hz
Nominal HP
1
/
4
1
/
3
1
/
2
3
/
4
11
1
/
2
23
115-1-60
5.2 6.0 8.6 13.3 14.4 ——
208-1-60
3.0 3.6 4.8 6.5 7.4 9.4 11.0
230-1-60
2.5 3.0 4.2 6.6 6.0 9.0 10.9
277-1-60
2.1 2.5 3.6 5.1 5.4 8.5 8.0
208-3-60
——2.4 3.6 3.8 6.0 6.5 8.2
230-3-60
——2.2 3.0 3.2 4.8 6.2 8.0
460-3-60
——1.1 1.5 1.9 2.8 3.1 4.0
Electrical data